Lcd Option Board Troubleshooting; Symptom At Power On Or During Operation; Communication Error Message During Operation; Trouble Shooting - Omron CP1L-EL20DR-D Operation Manual

Sysmac cp series cp1l-el/em cpu unit
Table of Contents

Advertisement

Trouble Shooting

11-7 Trouble Shooting

11-7-1 Symptom at Power ON or during Operation

Symptom
No LCD display
Display EEPROM Error
Screen and blinking red back-
light
Display NG Screen
Display Error Screen and
blinking red backlight
Button unresponsing
Display too faint
Note

11-7-2 Communication Error Message during Operation

Error message
Parity Error or Framing Error
or Overrun Error
FCS Error(Sum check)
Buffer overflow
Connecting Host...
Response code Error
630
Probable cause
LCD connection error or no power supply
from PLC.
Still in startup waiting time.
EEPROM is damaged.
User settings in EEPROM are corrupted.
LCD connection error.
Communication error between LCD and
PLC.
PLC error
Button is damaged.
User setting error.
Noise disturbing.
Backlight is damaged.
Contrast level is too low or too high.
Do not repair the LCD Option Board by yourself.
When communication error occurs, the error message will be displayed at the
LCD Option Board and the red backlight will blink.
Probable cause
Communication parameters or conditions of
PLC are changed.
LCD connection error.
Noise disturbing.
Noise disturbing.
The length of receiving data is beyond the
range of receiving memory.
Noise disturbing.
LCD connection error.
The communication between PLC and LCD
is out of service.
Operation mistake.
Noise disturbing.
CX-Programmer and LCD execute some
function at the same time.
Section 11-7
Possible solution
Check if LCD is connected correctly and the
PLC power supply is normal.
It's not error. Just wait a moment.
Replace the LCD Option Board.
Press the ESC button to exit the screen.
User settings backed up in EEPROM will be
replaced by default settings. Then proceed
to reset the screens. (See 11-7-3 for
details.)
Check if LCD is connected correctly.
Check the communication setting of PLC,
switching DipSW4 to ON.
Check PLC according to error code and
eliminate the error.
Replace the LCD Option Board.
Check the settings and change it.
Retry after the noise is reduced.
Replace the LCD Option Board.
Reset the contrast level.
Possible solution
Check the communication setting of PLC.
Check if LCD is still connected correctly.
• Return to normal automatically when the
noise is reduced.
• If the display cannot return to normal,
press the ESC button to restart LCD.
• Return to normal automatically when the
noise is reduced.
• If the display cannot return to normal,
press the ESC button to restart LCD.
Press the ESC button to restart LCD.
Check if LCD is still connected correctly.
Check if PLC is running normally.
Refer to CJ/CS Communication Manual for
solutions according to an end code.
• Return to normal automatically if the noise
is reduced.
• Press the ESC button to exit the screen.
Press the ESC button to exit the screen.
Execute this function by either CX-Pro-
grammer or LCD.