Analog Input Option Board Specifications - Omron CP1L-EL20DR-D Operation Manual

Sysmac cp series cp1l-el/em cpu unit
Table of Contents

Advertisement

Analog Input Option Board
10-5 Analog Input Option Board
Main Analog Input Option Board Specifications
Item
Input signal range
Max. rated input
External input impedance
Resolution
Overall accuracy
A/D conversion data
Averaging function
Conversion time
Isolation method
Current consumption
Analog Input Signal
Ranges
Each CP1W-ADB21 Analog Input Option Board provides two analog inputs.
• The analog input signal ranges are 0 to 10 V (with a resolution 1/4,000)
and 0 to 20 mA (with a resolution 1/2,000).
Voltage Input
0 V to 10 V
0 V to 15 V
200 kΩ min.
1/4000 (full scale)
25°C: ±0.5% (full scale)
0 to 55°C: ±1.0% (full scale)
0000 to 0FA0 hex
Not supported
Inner sample time 2ms/point
Refresh time > 6ms basing on baud rate and PLC cycle time
None
5 VDC: 20 mA max.
Analog input data is digitally converted according to the input signal range as
shown below.
Note When the input exceeds the specified range, the A/D conversion data will be
fixed at either the lower limit or upper limit.
■ 0 to 10 V
The 0 to 10 V range corresponds to the hexadecimal values 0000 to 0FA0 (0
to 4000). The entire data range is 0000 to 0FFF (0 to 4095).
Converted Data
Hexadecimal (Decimal)
0FFF(4095)
0FA0(4000)
0000(0)
0V
Specifications
Current Input
0 mA to 20 mA
0 mA to 30 mA
Approx. 250 Ω
1/2000 (full scale)
25°C: ±0.6% (full scale)
0 to 55°C: ±1.2% (full scale)
0000 to 07D0 hex
10V 10.24V
Section 10-5