Omron CP1L-EL20DR-D Operation Manual page 573

Sysmac cp series cp1l-el/em cpu unit
Table of Contents

Advertisement

Temperature Sensor Units
Setting Temperature Ranges
Note
!Caution Set the temperature range according to the type of temperature sensor con-
!Caution Do not set the temperature range to any values other than those for which
Note
(1) Always turn OFF the power supply before setting the temperature range.
(2) Never touch the DIP switch during Temperature Sensor Unit operation.
Static electricity may cause operating errors.
DIP Switch Settings
nected to the Unit. Temperature data will not be converted correctly if the tem-
perature range does not match the sensor.
temperature ranges are given in the following table. An incorrect setting may
cause operating errors.
The DIP switch is used to set the temperature unit and to set the temperature
input range.
ON
OFF
SW
1
Input type
2
Temperature unit
Temperature input
Input type
Range (°C)
−200.0 to 1300.0
K
−100.0 to 850.0
J
Fahrenheit temperature uses the following equation to convert the tempera-
ture unit from Celsius, but the temperature input range is different between
Fahrenheit and Celsius.
Fahrenheit temperature (°F) = Celsius temperature (°C) × 1.8 + 32
Setting
ON
J
OFF
K
ON
°F
OFF
°C
Range (°F)
−300.0 to 2300.0
−100.0 to 1500.0