Cpu Errors; Errors Created With Fals Instructions; Ethernet Controller Stop Error - Omron CP1L-EL20DR-D Operation Manual

Sysmac cp series cp1l-el/em cpu unit
Table of Contents

Advertisement

Troubleshooting

Errors Created with FALS Instructions

Probable cause
FALS instruction executed (FALS number 001)

Ethernet Controller Stop Error

Probable cause
ON when the Ethernet controller stops because of sum
value of MAC address error or controller error.

12-2-4 CPU Errors

CPU Errors
642
■ Reference Information
Error flag
FALS Error Flag, A401.06
Error code (A400) C101 to C2FF
Error information
---
■ Reference Information
Error flag
Ethernet Controller Stop Address Error,
A401.04
Error code (A400)
80F6
Error information
---
■ CPU Unit Indicators
POWER
RUN
ERR/ALM
INH
LNK/ACT
BKUP
A CPU error or fatal error may have occurred if the ERR/ALM indicator lights
during operation (RUN mode or MONITOR mode), the RUN indicator turns
OFF, and operation stops.
Probable cause
A WDT (watchdog) error occurred in the
CPU Unit. (This does not occur in normal
use.)
■ Reference Information
Error flag
None
Error code (A400)
None
Error information
None
Possible remedy
C100 hex will be added to the FALS number (001 to 1FF hex)
and the result will be stored in A400 as the error code (C100 to
C2FF hex).
Check the conditions for executing FALS instructions and
remove any causes for the user-defined error.
Possible remedy
Cycle the power supply. The Unit may be faulty. Consult your
OMRON representative.
POWER
RUN
ERR/ALM
INH
BKUP
LNK/ACT
Cycle the power supply. The Unit may be
faulty. Consult your OMRON representa-
tive.
Section 12-2
Lit
Not lit
Lit
---
---
---
Possible remedy