Specifications
42
(2) With the CP1W-32ER/CP1W-16ER, the load current is restricted de-
pending on the ambient temperature. Design the system considering the
load current based on the following graph.
100
(3) CP1W-32ER's maximum number of simultaneously ON output points is
24 (75%). Design the system considering the simultaneously ON points
and load current based on the following curve.
(4) There are restrictions imposed by the ambient temperature.
Relay Output Load Current Derating Curves for Expansion I/O Units (CP1W-
8ER/16ER/20EDR1/32ER/40EDR)
Added to CP1L-EL20DR-D
100%
Power voltage:
21.6 VDC
50%
Power voltage:
20.4 VDC
0%
55 °C
40
50
Ambient temperature
Added to CP1L-EL20DT@-D
100%
Power voltage:
21.6 VDC
50%
Power voltage:
20.4 VDC
0%
55 °C
40
50
Ambient temperature
50
0
43
Ambient temperature(˚C)
75
0
Ambient temperature(˚C)
Added to CP1L-EM30DR-D
100%
Power voltage:
21.6 VDC
50%
Power voltage:
20.4 VDC
0%
35
45
Ambient temperature
Added to CP1L-EM30DT@-D
100%
Power voltage:
21.6 VDC
50%
Power voltage:
20.4 VDC
0%
35
45
Ambient temperature
Section 2-2
55
55
Added to CP1L-EM40DR-D
100%
Power voltage:
21.6 VDC
50%
Power voltage:
20.4 VDC
0%
55 °C
35
45
Ambient temperature
Added to CP1L-EM40DT@-D
100%
Power voltage:
21.6 VDC
50%
Power voltage:
20.4 VDC
0%
55 °C
35
45
Ambient temperature
55 °C
55 °C