Wiring CP1L-EL/EM CPU Units

Output Wiring Precautions

Output Short-circuit
Protection
Connecting to a TTL
Circuit
Inrush Current
Considerations
86
Program Example
In this example, the sensor's power supply voltage is provided to input bit CIO
0.00 and a 100-ms timer delay (the time required for an OMRON Proximity
Sensor to stabilize) is created in the program. After the Completion Flag for
the timer turns ON, the sensor input on input bit CIO 0.01 will cause output bit
CIO 100.00 to turn ON.
0.00
T100
0.01
If a load connected to the output terminals is short-circuited, output compo-
nents and the printed circuit boards may be damaged. To guard against this,
incorporate a fuse in the external circuit. Use a fuse with a capacity of about
twice the rated output.
A TTL circuit cannot be connected directly to a transistor output because of
the transistor's residual voltage. It is necessary to connect a pull-up resistor
and a CMOS IC between the two.
When connecting a transistor or triac output to a load having a high inrush
current (such as an incandescent lamp), steps must be taken to avoid dam-
age to the transistor or triac. Use either of the following methods to reduce the
inrush current.
Example Method 1
OUT
SYSMAC CP1L-EL/EM
COM
Use a dark current of approximately 1/3 the rated current of the incandescent lamp.
Example Method 2
OUT
SYSMAC CP1L-EL/EM
COM
Install a limit resistance.
TIM
100
#0001
100.00
L
+
R
R
L
+
Section 3-4