CPU Unit Operating Modes
I/O Memory
Hold Bit status
Mode changed
(A500.12)
between
PROGRAM
and RUN/
MONITOR
OFF
Cleared
ON
Held
2-5-4

Startup Mode Setting

PLC Setup
Note
Note
2. The cycle time will increase by approximately 10 ms when the operating
mode is changed from MONITOR to RUN mode. This will not, however,
cause an error for exceeding the maximum cycle time limit.
I/O Memory
Operation stopped
Fatal error
other than
FALS
Cleared
Held
Held
Held
Note Refer to SECTION 4 I/O Memory Allocation.
This setting in the PLC Setup determines the operating mode that will be used
by the CPU Unit when the power supply is turned ON.
Name
Startup Mode
Specifies the
CPU Unit oper-
ating mode at
startup
A Programming Console cannot be connected to the CP1L-EL/EM.
A Programming Console cannot be connected to a CP1L-EL/EM CPU Unit. If
Use programming console is set, the CPU Unit will start in RUN mode.
Output bits allocated to Output Units
Mode changed
between
FALS
PROGRAM
executed
and RUN/
MONITOR
OFF
Held
Description
• Program (See note.)
• Monitor
• Run
• Use programming console
Section 2-5
Operation stopped
Fatal error
other than
executed
FALS
OFF
OFF
OFF
OFF
Settings
Default
Use program-
ming console
(See note.)
FALS
57