Rotary Switch Setting; Connecting Temperature Sensors; Thermocouples - Omron CP1L-EL20DR-D Operation Manual

Sysmac cp series cp1l-el/em cpu unit
Table of Contents

Advertisement

Temperature Sensor Units
!Caution Set the temperature range according to the type of temperature sensor con-
!Caution Do not set the temperature range to any values other than those for which
Setting
Input type
0
K
1
2
J
3
4 to F
---
Connecting Temperature
Sensors
516

Rotary Switch Setting

nected to the Unit. Temperature data will not be converted correctly if the tem-
perature range does not match the sensor.
temperature ranges are given in the following table. An incorrect setting may
cause operating errors.
The rotary switch is used to set the temperature range.
CP1W-TS001/002
Range (°C)
Range (°F)
−200 to 1,300
−300 to 2,300
0.0 to 500.0
0.0 to 900.0
−100 to 850
−100 to 1,500
0.0 to 400.0
0.0 to 750.0
Cannot be set.

Thermocouples

CP1W-TS001
Either K or J thermocouples can be connected, but both thermocouples must
be the same type and the same input range.
Temperature input 0
Temperature input 1
CP1W-TS002
Either K or J thermocouples can be connected, but all four thermocouples
must be the same type and the same input range.
Input type
Pt100
JPt100
---
---
---
Input 0
Input 1
+
+
NC
NC
Input 0
Input 1
Cold junction compensator
Section 9-5
CP1W-TS101/102
Range (°C)
Range (°F)
−200.0 to 650.0
−300.0 to
1,200.0
−200.0 to 650.0
−300.0 to
1,200.0
Cannot be set.
NC
NC
NC
NC
NC
NC