Transistor Outputs (Sinking Or Sourcing); Normal Outputs - Omron CP1L-EL20DR-D Operation Manual

Sysmac cp series cp1l-el/em cpu unit
Table of Contents

Advertisement

Specifications
Note

Transistor Outputs (Sinking or Sourcing)

Normal Outputs

Item
Max. switching
4.5 to 30 VDC, 300 mA/output, 0.9 A/common, EM40D@-D 3.6 A/Unit
capacity
Min. switching capacity 4.5 to 30 VDC, 1 mA
Leakage current
0.1 mA max.
Residual voltage
0.6 V max.
ON delay
0.1 ms max.
OFF delay
0.1 ms max.
38
(1) Under the worst conditions, the service life of output contacts is as shown
above. The service life of relays is as shown in the following diagram as
a guideline.
500
125 VAC resistive load
300
200
30 VDC/250 VAC resistive load
100
50
30
20
10
5
125 VAC cosφ = 0.4
3
250 VAC cosφ = 0.4
2
0.1
0.2 0.3 0.5 0.7 1
Contact current (A)
(2) There are restrictions imposed by the ambient temperature.
CPU Units with Relay Outputs (CP1L-E@@@DR-D)
Relay Output Load Current Derating Curves for CPU Units and Expansion
I/O Units
CP1L-EL20DR-D
100%
Power voltage:
21.6 VDC
50%
Power voltage:
20.4 VDC
0%
40
45
55°C
Ambient temperature
Note The above restrictions, apply to the relay output load current from
the CPU Unit even if Expansion I/O Units are not connected.
CIO 100.00 to CIO 100.03
30 VDC τ = 7 ms
2
3
5
10
CP1L-EM30DR-D
100%
Power voltage:
21.6 VDC
50%
Power voltage:
20.4 VDC
0%
55 °C
35
45
Ambient temperature
Specification
CIO 100.04 to CIO 101.07 (See note.)
EM30D@-D 2.7 A/Unit
EL20D@-D 1.8 A/Unit
1.5 V max.
1 ms max.
Section 2-2
CP1L-EM40DR-D
100%
Power
voltage:
21.6 VDC
50%
Power
voltage:
20.4 VDC
0%
55 °C
30
35
50
Ambient temperature

Hide quick links: