Program Protection

8-7
Program Protection
8-7-1

Read Protection

Overview
Read Protection Using
Extended Passwords
Operating Procedure

Setting Protection

1,2,3...
The following protection functions are supported by the CP1L-EL/EM CPU
Units.
• Read protection from the CX-Programmer
• Write protection using a DIP switch setting
• Write protection setting from the CX-Programmer
• Write protection against FINS commands sent to the CPU Unit via net-
works
• Prohibiting creating a program file for file memory
It is possible to read-protect individual program tasks (called task read protec-
tion) or the entire user program (called UM read protection).
Read protection prevents anyone from displaying or editing the read-protected
set of tasks or entire user program from CX-Programmer without inputting the
correct password. If the password is input incorrectly five times consecutively,
password input will be disabled for two hours, providing even better security
for PLC data.
With unit version 1.1 or later and CX-Programmer version 9.6 or higher, you
can extend protection with UM read protection and task read protection to
ensure better protection for your design assets.
Register a password either online or offline.
1. Select the PLC name, then select View - Properties.
2. Click the Protection Tab in the PLC Properties Dialog Box and enter the
passwords.