Analog Inputs - Omron CP1L-EL20DR-D Operation Manual

Sysmac cp series cp1l-el/em cpu unit
Table of Contents

Advertisement

Temperature Sensor Units
2-core shielded
twisted-pair cable
+
Analog
device with
voltage
output
Note
Analog Input Signal
Ranges
532

Analog Inputs

Last two channels can be used as analog inputs, but two of the analog inputs
must be the same range.
LOOP0−
Temperature input 0
Temperature input 1
Wiring for Analog Inputs
V IN
Analog
I IN
Input 2, 3
COM
FG
(1) When an input is not being used, short the + and – terminals.
(2) Separate wiring from power lines (AC power supply lines, high-voltage
lines, etc.)
(3) When there is noise in the power supply line, install a noise filter on the
input section and the power supply.
When the input exceeds the specified range, the AD converted data will be
fixed at either the lower limit or upper limit.
0 to 10 V
The 0 to 10 V range corresponds to the hexadecimal values 0000 to 2EE0 (0
to 12000). The entire data range is FDA8 to 3138 (−600 to 12600). A negative
voltage is expressed as a two's complement.
Converted Data
Hexadecimal (Decimal)
3138 (12600)
2EE0 (12000)
−0.5 V
0000 (0)
LOOP0+
LOOP1+
NC
NC
LOOP1−
Cold junction
compensator
2-core shielded
twisted-pair cable
+
Analog
device with
current
output
10 V 10.5 V
0 V
FDA8 (−600)
Section 9-5
LOOP2+
LOOP3+
I IN3
V IN2
V IN3
LOOP2−
LOOP3−
I IN2
COM2
COM3
Analog
Analog
device
device
with
with
voltage
current
output
output
Analog
Analog
input 2
input 3
V IN
Analog
I IN
Input 2, 3
COM
FG

Hide quick links: