Cj1W-Od201 Transistor Output Unit (8 Points) - Omron CJ2 CPU UNIT User Manual

Cj2 cpu unit hardware
Hide thumbs Also See for CJ2 CPU UNIT:
Table of Contents

Advertisement

CJ1W-OD201 Transistor Output Unit (8 Points)

Name
Model
Rated Voltage
Operating Load Voltage Range
Maximum Load Current
Maximum Inrush Current
Leakage Current
Residual Voltage
ON Response Time
OFF Response Time
Insulation Resistance
Dielectric Strength
Number of Circuits
Internal Current Consumption
Fuse
External Power Supply
Weight
Circuit Configuration
Terminal Connections
*1 Terminal numbers A0 to A8 and B0 to B8 are used in this manual, but they are not printed on the Unit.
Note Although 16 I/O bits (1 word) are allocated, only 8 of these can be used for external I/O. This Unit is also
treated as a 16-point I/O Unit in the I/O tables.
CJ2 CPU Unit Hardware User's Manual
8-point Transistor Output Unit with Terminal Block (Sinking Outputs)
CJ1W-OD201
12 to 24 VDC
10.2 to 26.4 VDC
2.0 A/point, 8.0 A/Unit
10 A/point, 10 ms max.
0.1 mA max.
1.5 V max.
0.5 ms max.
1.0 ms max.
20 MΩ between the external terminals and the GR terminal (100 VDC)
1,000 VAC between the external terminals and the GR terminal for
1 minute at a leakage current of 10 mA max.
8 (4 points/common, 2 circuits)
90 mA max.
6.3 A (1/common, 2 used)
The fuse cannot be replaced by the user.
12 to 24 VDC, 10 mA min.
110 g max.
Fuse
Output indicator
Fuse
*1
Signal
Signal
Connec-
tor pin
name
name
OUT0
A0
L
OUT1
B0
OUT2
L
A1
OUT3
B1
NC
A2
12 to 24 VDC
NC
B2
COM0
A3
+V
B3
NC
A4
NC
B4
OUT4
L
A5
OUT5
B5
OUT6
L
A6
OUT7
B6
NC
A7
NC
12 to 24 VDC
B7
COM1
A8
+V
B8
• When wiring, pay careful attention to the polarity of the external power
supply. The load may operate incorrectly if the polarity is reversed.
Appendices
Signal
name
+V
OUT0
to
OUT3
COM0
+V
OUT4
to
OUT7
COM1
L
L
L
L
A-23

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents