Variable Duty Factor Pulse Outputs (Pwm(891) Outputs) - Omron CP1H-X40D Operation Manual

Cpu unit sysmac cp series
Hide thumbs Also See for CP1H-X40D:
Table of Contents

Advertisement

Pulse Outputs
5-3-9

Variable Duty Factor Pulse Outputs (PWM(891) Outputs)

Overview
Bit Allocations
Procedure
Determine the pulse output port.
Wire the outputs.
PLC Setup settings
(Y models only)
Ladder program
Restrictions on the PWM(891) Outputs
Specifications
Note
290
PWM (Pulse Width Modulation) pulse outputs can be output with a specified
duty factor. The duty factor is the ratio of the pulse's ON time and OFF time in
one pulse cycle. Use the PWM(891) instruction to generate variable duty fac-
tor pulses from a built-in output.
The duty factor can be changed while pulses are being output.
Word
Bit
CIO 101
00
01
• PWM output 0 or PWM output 1
• Disable the origin search function for pulse
outputs 2 and 3.
Note: Disable the origin search function because the PWM output
shares the output with the origin search function's Error
Counter Reset Output and both cannot be used
simultaneously.
Execute PWM(891).
• In the Y CPU Units, PWM outputs 0 and 1 cannot be used for pulse out-
puts 2 and 3 if the origin search function is enabled for pulse outputs 2
and 3.
Item
Duty factor
Frequency
Output mode
Instruction
The frequency can be set up to 6553.5 Hz in the PWM(891) instruction, but
the duty factor accuracy declines significantly at high frequencies because of
limitations in the output circuit at high frequencies.
Function
PWM output 0
PWM output 1
Specifications
0.0% to 100.0% in 0.1% increments
(Duty factor accuracy is ±5% at 1 kHz.)
0.1 Hz to 6,553.5 Hz
Set in 0.1 Hz units. (See note.)
Continuous mode
PWM(891)
Section 5-3

Advertisement

Table of Contents
loading

This manual is also suitable for:

Cp1h-xa40dCp1h-y20dt-dCp1h

Table of Contents