Sequence Output Instructions; Out/Out Not - Omron SYSMAC CP Series Instruction & Reference Manual

Cpu unit
Hide thumbs Also See for SYSMAC CP Series:
Table of Contents

Advertisement

2 Instructions

Sequence Output Instructions

OUT/OUT NOT

Instruction
OUTPUT
OUTPUT NOT
Symbol
Applicable Program Areas
Area
Step program areas
Usage
OK
Operands
Operand
---
Operand Specifications
Area
CIO
WR
OUT
OK
OK
OUT NOT
Flags
There are no flags affected by this instruction.
Function
OUT
If there is no immediate refreshing specification, the status of the execution condition (power flow) is
written to the specified bit in I/O memory. If there is an immediate refreshing specification, the status of
the execution condition (power flow) is also written to the CPU Unit's built-in output terminal in addition
to the output bit in I/O memory.
OUT NOT
If there is no immediate refreshing specification, the status of the execution condition (power flow) is
reversed and written to a specified bit in I/O memory. If there is an immediate refreshing specification,
the status of the execution condition (power flow) is reversed and also written to the CPU Unit's built-in
output terminal in addition to the output bit in I/O memory.
2-18
Mnemonic
Variations
OUT
!OUT
OUT NOT
!OUT NOT
OUT
Description
---
Word addresses
HR
AR
T
C
DM
OK
OK
---
---
OK
Function
code
Outputs the result (execution condition) of the
---
logical processing to the specified bit.
Reverses the result (execution condition) of the
---
logical processing, and outputs it to the specified
bit.
Subroutines
OK
Data type
BOOL
Indirect DM addresses
Constants
@DM
*DM
---
---
---
CP1E CPU Unit Instructions Reference Manual(W483)
Function
OUT NOT
Interrupt tasks
OK
Size
---
CF
Pulse bits
TR bits
---
---
OK

Hide quick links: