H2: Multi-Function Digital Outputs

No.
(Addr.
Name
Hex)
Terminal M1-M2
H2-01
function selection
(40B)
(relay)
Terminal M3-M4
H2-02
function selection
(40C)
(relay)
Terminal M5-M6
H2-03
function selection
(40D)
(relay)
H2-oo
Function
Setting
0
During run
1
Zero speed
2
Speed agree 1
3
User-set speed agree 1
4
Frequency detection 1
5
Frequency detection 2
6
Drive ready
7
DC bus undervoltage
8
During baseblock (N.O.) BaseBlk 1
Frequency reference
9
source
A
Run command source
Torque detection 1
B
(N.O.)
C
Frequency reference loss Loss of Ref
E
Fault
F
Through mode
10
Minor fault
Fault reset command
11
active
12
Timer output
13
Speed agree 2
14
User-set speed agree 2
15
Frequency detection 3
16
Frequency detection 4
Torque detection 1
17
(N.C.)
1A
During Reverse
1B
During baseblock (N.C.) BaseBlk 2
1E
Restart enabled
Motor overload alarm
1F
(oL1)
YASKAWA TOEP YAIZ1U 03B YASKAWA AC Drive – Z1000 User Manual
LCD Display
Refer to H2 Multi-Function Digital Output Settings on pages
M1-M2 Func Sel
293
to
294
M3/M4 Func Sel
M5/M6 Func Sel
H2 Multi-Function Digital Output Settings
LCD Display
During RUN 1
Closed: A Run command is active or voltage is output.
Open: Output frequency is above the minimum output frequency set in E1-09.
Zero Speed
Closed: Output frequency is below the minimum output frequency set in E1-09.
Closed: Output frequency equals the speed reference (plus or minus the hysteresis
Fref/Fout Agree1
set to L4-02).
Closed: Output frequency and speed reference equal L4-01 (plus or minus the
Fref/Set Agree 1
hysteresis set to L4-02).
Closed: Output frequency is less than or equal to the value in L4-01 with hysteresis
Freq Detect 1
determined by L4-02.
Closed: Output frequency is greater than or equal to the value in L4-01 with
Freq Detect 2
hysteresis determined by L4-02.
Drive Ready
Closed: Power up is complete and the drive is ready to accept a Run command.
DC Bus Undervolt
Closed: DC bus voltage is below the Uv trip level set in L2-05.
Closed: Drive has entered the baseblock state (no output voltage).
Open: External Reference 1 or 2 supplies the frequency reference (set in b1-01 or
Ref Source
b1-15).
Closed: HOA keypad supplies the frequency reference.
Open: External Reference 1 or 2 supplies the Run command (set in b1-02).
Run Cmd Source
Closed: HOA keypad supplies the Run command.
Closed: An overtorque or undertorque situation has been detected.
Trq Det 1 N.O.
Closed: Analog frequency reference has been lost.
Fault
Closed: Fault occurred.
Not Used
Set this value when using the terminal in the pass-through mode.
Closed: An alarm has been triggered, or the IGBTs have reached 90% of their
Minor Fault
expected life span.
Closed: A command has been entered to clear a fault via the input terminals or
Reset Cmd Active
from the serial network.
Timer Output
Closed: Timer output.
Fref/Fout Agree2
Closed: When drive output frequency equals the frequency reference ±L4-04.
Fref/Set Agree 2
Closed: When the drive output frequency is equal to the value in L4-03 ±L4-04.
Closed: When the drive output frequency is less than or equal to the value in L4-03
Freq Detect 3
±L4-04.
Closed: When the output frequency is greater than or equal to the value in L4-03
Freq Detect 4
±L4-04.
Open: Overtorque or undertorque has been detected.
Trq Det 1 N.C.
Reverse Dir
Closed: Drive is running in the reverse direction.
Open: Drive has entered the baseblock state (no output voltage).
Dur Flt Restart
Closed: An automatic restart is performed
Closed: oL1 is at 90% of its trip point or greater. An oH3 situation also triggers
Overload (OL1)
this alarm.
B.7 H Parameters: Multi-Function Terminals
Description
for descriptions of setting values.
Description
Values
Page
Default: 0
Range: 0 to 1B2
Default: 1
Range: 0 to 1B2
Default: 2
Range: 0 to 1B2
Page
B
293