4.7 Basic Drive Setup Adjustments
n
E1-01: Input Voltage Setting
Adjusts the levels of some protective features of the drive (overvoltage, Stall Prevention, etc.). Set this parameter to the nominal
voltage of the AC power supply.
NOTICE: Set parameter E1-01 to match the input voltage of the drive. Drive input voltage (not motor voltage) must be set in E1-01 for the
protective features to function properly. Failure to set the correct drive input voltage will result in improper drive operation.
No.
E1-01
E1-01 Related Values
The input voltage setting determines the overvoltage and undervoltage detection levels, the KEB function, and the overvoltage
suppression function.
Voltage
600 V Class
n
V/f Pattern Settings E1-04 to E1-13
If E1-03 is set to a preset V/f pattern (i.e., a value other than F), the user can monitor the V/f pattern in parameters E1-04
through E1-13. To create a new V/f pattern, set E1-03 to F.
pattern.
Note:
Certain E1-oo parameters might not be visible depending on the control mode.
No.
E1-04
E1-05
E1-06
E1-07
E1-08
E1-09
E1-10
E1-11
E1-12
E1-13
<1> Default setting is dependent on parameter A1-02, Control Mode Selection.
<2> Default setting is dependent on parameter o2-04, Drive Model Selection.
<3> Parameter ignored when E1-11 and E1-12 are set to 0.0.
Note:
1. The following condition must be true when setting up the V/f pattern: E1-09 ≤ E1-07 < E1-06 ≤ E1-11 ≤ E1-04
2. To make the V/f pattern a straight line below E1-06, set E1-09 equal to E1-07. In this case the E1-08 setting is disregarded.
3. E1-03 is unaffected when the drive is initialized, but E1-04 through E1-13 return to their default values.
4. Only use E1-11, E1-12, and E1-13 to fine-tune the V/f pattern in the constant output range. These parameters rarely need to be changed.
128
Parameter Name
Input Voltage Setting
Setting Value of E1-01
All settings
Parameter Name
Maximum Output Frequency
Maximum Voltage
Base Frequency
Middle Output Frequency
Middle Output Frequency Voltage
Minimum Output Frequency
Minimum Output Frequency Voltage
Middle Output Frequency 2
Middle Output Frequency Voltage 2
Base Voltage
Output Voltage (V)
E1-05
E1-12
E1-13
E1-08
E1-10
Figure 4.22 V/f Pattern
Setting Range
445.6 to 733.1 V
Refer to V/f Pattern on page 128
Refer to Parameter List on page 269
E1-09
E1-07 E1-06 E1-11 E1-04
Frequency (Hz)
YASKAWA TOEP YAIZ1U 03B YASKAWA AC Drive – Z1000 User Manual
(Approximate Values)
Uv Detection Level (L2-05)
475 V
for an example custom V/f
Setting Range
40.0 to 240.0 Hz
0.0 to 733.1 V
0.0 to 240.0 Hz
0.0 to 240.0 Hz
0.0 to 733.1 V
0.0 to 240.0 Hz
0.0 to 733.1 V
0.0 to 240.0 Hz
0.0 to 733.1 V
0.0 to 733.1 V
Default
661.3 V
for details.
Default
<1>
<1>
<1>
30.0 Hz
143.8 V
<1>
<2>
<3>
0.0 Hz
<3>
0.0 V
0.0 V