YASKAWA Z1000 User Manual page 201

Ac drive for hvac fan and pump
Hide thumbs Also See for Z1000:
Table of Contents

Advertisement

Digital Operator Display
CPF11 to CPF14
or
CPF16 to CPF19
Cause
There is a self-diagnostic error in the control
circuit
Connector on the operator is damaged
Digital Operator Display
Cause
Control circuit is damaged
Digital Operator Display
Cause
There is a connection error
Drive fails to operate properly due to electrical
signal interference
Digital Operator Display
Cause
There is an error in EEPROM control circuit
The power supply was switched off while
parameters were being saved to the drive
Digital Operator Display
Cause
There is a faulty connection between the
terminal board and the control board
Digital Operator Display
CPF20 or CPF21
or
Cause
Hardware is damaged
YASKAWA TOEP YAIZ1U 03B YASKAWA AC Drive – Z1000 User Manual
Control Circuit Error
• Cycle power to the drive.
• If the problem continues, replace the control board or the entire drive. Contact Yaskawa or a Yaskawa
representative for instructions on replacing the control board.
Replace the operator.
A/D Conversion Error
CPF02
An A/D conversion error or control circuit error occurred.
• Cycle power to the drive.
• If the problem continues, replace the control board or the entire drive. Contact Yaskawa or a Yaskawa
representative for instructions on replacing the control board.
Control Board Connection Error
CPF03
Connection error between the control board and the drive
• Turn off the power and check the connection between the control board and the drive.
• If the problem continues, replace the control board or the entire drive. Contact Yaskawa or a Yaskawa
representative for instructions on replacing the control board.
• Check the various options available to minimize the effects of noise.
• Counteract noise in the control circuit, main circuit, and ground wiring.
• Use only recommended cables or other shielded line. Ground the shield on the controller side or the
drive input power side.
• Ensure that other equipment such as switches or relays do not cause noise. Use surge suppressors if
required.
• Separate all communication wiring from drive power lines. Install an EMC noise filter to the drive
power supply input.
EEPROM Memory Data Error
CPF06
Error in the data saved to EEPROM
• Turn off the power and check the connection between the control board and the drive.
• If the problem continues, replace the control board or the entire drive. Contact Yaskawa or a Yaskawa
representative for instructions on replacing the control board.
Reinitialize the drive (A1-03 = 2220, 3330).
CPF07
Terminal Board Connection Error
CPF08
• Turn off the power and reconnect the terminal board.
• If the problem continues, replace the control board or the entire drive. Contact Yaskawa or a Yaskawa
representative for instructions on replacing the control board.
Control Circuit Error
• Cycle power to the drive.
• If the problem continues, replace the control board or the entire drive. Contact Yaskawa or a Yaskawa
representative for instructions on replacing the control board.
Fault Name
Possible Solution
Fault Name
Possible Solution
Fault Name
Possible Solution
Fault Name
Possible Solution
Fault Name
Possible Solution
Fault Name
Possible Solution
5.4 Fault Detection
5
201

Advertisement

Table of Contents
loading

Table of Contents