S6: Z1000 Protection - YASKAWA Z1000 User Manual

Ac drive for hvac fan and pump
Hide thumbs Also See for Z1000:
Table of Contents

Advertisement

B.11 S: Special Application
No.
(Addr.
Name
Hex)
HAND Key Function
S5-07
Selection (HOA
(3235)
Keypad)
u

S6: Z1000 Protection

No.
(Addr.
Name
Hex)
S6-01
Emergency Override
(3236)
Speed
S6-02
Emergency Override
(3237)
Reference Selection
S6-03
ov2 Detect Time
(3238)
Output Phase Loss
S6-07
Detection Level for
(323C)
Dynamic Audible Noise
Control
314
LCD Display
Determines whether the HAND key on the HOA keypad will
Oper HAND Key
be enabled for switching between HAND and AUTO.
0: Disabled
0: Disabled
1: Enabled
1: Enabled
LCD Display
Sets the speed command used in Emergency Override mode when
S6-02 = 0.
E Override Speed
Selects the frequency reference source for the Emergency
Override function (H1-oo= AF or B0).
E OverrideRefSel
0: Use S6-01 Reference
0: Use S6-01 Ref
1: Use AUTO Reference
1: Use AUTO Ref
Note:
Sets the detection time of ov2 in 0.1 s increments.
ov2 Detect Time
Sets the output phase loss detection level for Dynamic Audible
Noise Control. Decrease the setting in steps of 10% when output
Outp Ph Loss Lv1
phase loss is detected erroneously. This setting rarely needs to be
changed.
Description
Description
The Emergency Override inputs will function even
if the CALL alarm is displayed.
YASKAWA TOEP YAIZ1U 03B YASKAWA AC Drive – Z1000 User Manual
Values
Page
Default: 1
Range: 0, 1
Values
Page
Default: 0.00
Hz
Min.: 0.00
Max.: 240.00
Default: 0
Range: 0, 1
Default: 10.0 s
Min.: 0.0
Max.: 1200.0
Default:
100.0%
Min.: 10.0
Max.: 100.0

Advertisement

Table of Contents
loading