6.5 Installing Peripheral Devices
A – Power supply
B – Input-side noise filter
n
Output-Side Noise Filter
A noise filter on the output side of the drive reduces inductive noise and radiated noise.
output-side noise filter wiring.
NOTICE: Do not connect phase-advancing capacitors or LC/RC noise filters to the output circuits. Improper application of noise filters could
result in damage to the drive.
A – Power supply
B – Drive
• Radiated Noise: Electromagnetic waves radiated from the drive and cables create noise throughout the radio bandwidth
that can affect surrounding devices.
• Induced Noise: Noise generated by electromagnetic induction can affect the signal line and may cause the controller to
malfunction.
Preventing Induced Noise
Use a noise filter on the output side or use shielded cables. Lay the cables at least 30 cm away from the signal line to prevent
induced noise.
A – Power supply
B – Drive
C – Shielded motor cable
D – Motor
254
A
(model LNFD-oo)
Figure 6.10 Input-Side Noise Filter
A
MCCB
Figure 6.11 Output-Side Noise Filter
A
MCCB
R/L1
S/L2
T/L3
Figure 6.12 Preventing Induced Noise
B
MCCB
R/L1
R
U
S/L2
S
V
T/L3
T
W
E
MCCB
D
C – Drive
D – Other control device
B
C
R/L1
U/T1
1
4
S/L2
V/T2
2
5
T/L3
W/T3
3
6
C – Output-side noise filter
D – Motor
B
C
U/T1
V/T2
W/T3
E
G
E – Separate at least 30 cm
F – Controller
G – Signal line
YASKAWA TOEP YAIZ1U 03B YASKAWA AC Drive – Z1000 User Manual
C
Figure 6.11
illustrates an example of
D
M
D
M
F