YASKAWA Z1000 User Manual page 39

Ac drive for hvac fan and pump
Hide thumbs Also See for Z1000:
Table of Contents

Advertisement

n
Single Drive Installation
Figure 2.2
shows the installation distance required to maintain sufficient space for airflow and wiring. Install the heatsink
against a closed surface to avoid diverting cooling air around the heatsink.
A
A
A – 50 mm minimum
B – 30 mm minimum
Note:
IP20/NEMA 1, UL Type 1 enclosure and IP00/Open Type enclosure models require the same amount of space above and below the drive
for installation.
n
Multiple Drive Installation (Side-by-Side Installation)
Models 5A0003 to 5A0032 can take advantage of Side-by-Side installation.
When installing multiple drives into the same enclosure panel, mount the drives according to
Installation Method Selection, to 1 (Side-by-Side Mounting).
When mounting drives with the minimum clearance of 2 mm according to
considering derating.
Refer to Parameter List on page 269
A – 50 mm minimum
B – 30 mm minimum
Note:
Align the tops of the drives when installing drives of different heights in the same enclosure panel. Leave space between the tops and bottoms
of stacked drives for easier cooling fan replacement.
YASKAWA TOEP YAIZ1U 03B YASKAWA AC Drive – Z1000 User Manual
Side Clearance
Top/Bottom Clearance
C
C
B
B
Figure 2.2 Correct Installation Spacing
Line up the tops of the drives.
Side Clearance
C
A
B
A
Figure 2.3 Space Between Drives (Side-by-Side Mounting)
D
C – 120 mm minimum
D – Airflow direction
Figure
2.3, set parameter L8-35 to 1 while
for details.
Top/Bottom Clearance
A
D
D
B
A
C – 2 mm minimum
D – 120 mm minimum
2.2 Mechanical Installation
D
Figure 2.2
and set L8-35,
2
39

Advertisement

Table of Contents
loading

Table of Contents