A.1 Power Ratings
u

Three-Phase 600 V Class Drive Models 5A0125 to 5A0242

Item
Drive Models
Maximum Applicable Motor Capacity (HP)
Input Current (A)
Input
Allowable Voltage Fluctuation
Allowable Frequency Fluctuation
Input Power (kVA)
Rated Output Capacity (kVA)
Rated Output Current (A)
Overload Tolerance
Output
Carrier Frequency
Maximum Output Voltage (V)
Maximum Output Frequency (Hz)
<1> The motor capacity (HP) refers to a NEC rated 4-pole motor. The rated output current of the drive output amps should be equal to or greater than
the motor current. Select the appropriate capacity drive if operating the motor continuously above motor nameplate current.
<2> Assumes operation at the rated output current. Input current rating varies depending on the power supply transformer, input reactor, wiring
connections, and power supply impedance.
<3> Rated motor capacity is calculated with a rated output voltage of 575 V.
<4> Carrier frequency can be increased to 2 kHz while keeping this current derating. Higher carrier frequency settings require derating.
260
Table A.3 Power Ratings Continued (Three-Phase 600 V Class)
<1>
<2>
Rated Voltage
Rated Frequency
<3> <4>
<4>
Specification
5A0125
5A0145
125
150
129
158
Three-phase 500 to 600 Vac 50/60 Hz
-10 (-15) to +10%
147
181
124
144
125
145
110% of rated output for 60 s
140% of rated output for 0.5 s
User adjustable between 2 and 3kHz
Three-phase 500 to 600 Vac (proportional to input voltage)
YASKAWA TOEP YAIZ1U 03B YASKAWA AC Drive – Z1000 User Manual
5A0192
200
228
±5%
261
191
192
240 Hz
5A0242
250
263
301
241
242

Advertisement

Table of Contents
loading

Table of Contents