H2: Multi-Function Digital Outputs - YASKAWA E1000 Technical Manual

For fan and pump
Table of Contents

Advertisement

5.7 H: Terminal Functions
Setting 90 to 97: DriveWorksEZ Digital Input 1 to 8
These settings are for digital inputs functions used in DriveWorksEZ. Normally there is no need to change these settings.
Setting 9F: DriveWorksEZ Disable
This function is used to enable or disable a DriveWorksEZ program in the drive. An input programmed for this function
is effective only if A1-07 = 2.
Status
Open
Closed

◆ H2: Multi-Function Digital Outputs

H2-01 to H2-03: Terminal M1-M2, M3-M4, and M5-M6 Function Selection
The drive has three multi-function output terminals.
H2-01, H2-02, and H2-03.
No.
H2-01
H2-02
H2-03
Setting
0
During Run
1
Zero Speed
2
Speed Agree 1
3
User-set Speed Agree 1
4
Frequency Detection 1
5
Frequency Detection 2
6
Drive Ready
7
DC Bus Undervoltage
8
During Baseblock (N.O.)
9
Frequency Reference Source
A
Run Command Source
B
Torque Detection 1 (N.O.)
C
Frequency Reference Loss
E
Fault
F
Through Mode
10
Minor Fault
11
Fault Reset Command Active
12
Timer Output
13
Speed Agree 2
14
User-set Speed Agree 2
15
Frequency Detection 3
16
Frequency Detection 4
17
Torque Detection 1 (N.C.)
1A
During Reverse
1B
During Baseblock (N.C.)
Setting 0: During Run
Output closes when the drive is outputting a voltage.
Status
Open
Drive is stopped.
Closed
A Run command is input or the drive is during deceleration or during DC injection.
190
DriveWorksEZ enabled
DriveWorksEZ disabled
Parameter Name
Terminal M1-M2 Function Selection (relays)
Terminal M3-M4 Function Selection (relays)
Terminal M5-M6 Function Selection (relays)
Table 5.29 Multi-Function Digital Output Terminal Settings
Function
Page
Description
Table 5.29
lists the functions available for theses terminals using
Setting
190
1E
Restart Enabled
191
1F
Motor Overload Alarm (oL1)
191
20
Drive Overheat Pre-alarm (oH)
192
2F
Maintenance Period
191
37
During Frequency Output
192
38
Drive Enable
193
39
Watt Hour Pulse Output
193
3A
Drive Overheat Alarm (oH2)
193
3B
RUN Command from Option Card/Communications
193
3C
LOCAL/REMOTE Status
193
3D
During Speed Search
194
3E
PI Feedback Low
194
3F
PI Feedback High
194
4A
During KEB Operation
194
4B
During Short Circuit Braking
194
4C
During Fast Stop
194
4D
oH Pre-alarm Time Limit
194
50
Waiting for Run
194
58
Underload Detection
195
60
Internal Cooling Fan Alarm
195
90
Driveworksez Digital Output 1
195
91
Driveworksez Digital Output 2
194
92
Driveworksez Digital Output 3
196
100 to 192
Functions 0 to 92 with Inverse Output
196
Description
YASKAWA ELECTRIC SIEP C710616 35D YASKAWA AC Drive E1000 Technical Manual
Setting Range
0 to 192
0: During run
0 to 192
1: Zero Speed
0 to 192
2: Speed agree 1
Function
Default
Page
196
196
196
197
197
197
197
197
197
197
197
197
198
198
198
198
198
198
198
198
198
198