4.13 Advanced Drive Setup Adjustments
Setting = C
90 Hz
575
34.5
17.3
0
1.5 3
60
90
Frequency (Hz)
n
H3-01: Terminal A1 Signal Level Selection
Selects the input signal level for analog input A1. Set jumper S1 on the terminal board accordingly for voltage input or current
input.
No.
H3-01
Setting 0: 0 to 10 V with Zero Limit
The input level is 0 to 10 Vdc with zero limit. The minimum input level is limited to 0%, so that a negative input signal due
to gain and bias settings will be read as 0%.
Setting 1: 0 to 10 V without Zero Limit
The input level is 0 to 10 Vdc without zero limit. If the resulting voltage is negative after being adjusted by gain and bias
settings, then the motor will rotate in reverse.
Setting 2: 4 to 20 mA Current Input
The input level is 4 to 20 mA. Negative input values by negative bias or gain settings are limited to 0%.
Setting 3: 0 to 20 mA Current Input
The input level is 0 to 20 mA. Negative input values by negative bias or gain settings are limited to 0%.
n
H3-02: Terminal A1 Function Selection
Selects the input signal level for analog input A1.
No.
H3-02
n
H3-09: Terminal A2 Signal Level Selection
Selects the input signal level for analog input A2. Set Jumper S1 on the terminal board accordingly for a voltage input or
current input.
No.
H3-09
Setting 0: 0 to 10 V with Zero Limit
The input level is 0 to 10 Vdc. Negative input values will be limited to 0.
page
170.
Setting 1: 0 to 10 V without Zero Limit
The input level is 0 to 10 Vdc. Negative input values will be accepted.
page
170.
Setting 2: 4 to 20 mA Current Input
The input level is 4 to 20 mA. Negative input values by negative bias or gain settings will be limited to 0%.
Setting 3: 0 to 20 mA Current Input
The input level is 0 to 20 mA. Negative input values by negative bias or gain settings will be limited to 0%.
170
Table 4.37 Constant Output, Settings C to F
Setting = D
120 Hz
575
34.5
17.3
0
1.5 3
60
120
Frequency (Hz)
Name
Terminal A1 Signal Level Selection
Name
Terminal A1 Function Selection
Name
Terminal A2 Signal Level Selection
Setting = E
180 Hz
575
34.5
17.3
0
1.5 3
60
180
Frequency (Hz)
Setting Range
Setting Range
Setting Range
Refer to Setting 0: 0 to 10 V with Zero Limit on
Refer to Setting 1: 0 to 10 V without Zero Limit on
YASKAWA TOEP YAIZ1U 03B YASKAWA AC Drive – Z1000 User Manual
Setting = F
575
143.8
17.3
0
1.5
30
Frequency (Hz)
Default
0 to 3
Default
0 to 41
Default
0 to 3
60 Hz
60
0
0
2