4.3 The Drive, Programming, and Clock Adjustment Modes
3
Press the ENTER key to enter select the parameter setting mode.
4
Use the up and down arrow keys to scroll through display menu until parameter o4-17 appears.
5
Press the ENTER key until "0" flashes.
6
Press the up arrow key so that the display changes to "1".
Press the ENTER key and the time setting screen will appear. Use the right arrow key to select
7
the desired digit, then set the correct date and time using the up and down arrow keys.
After entering the correct time, press the ENTER key to save the changes.
8
The display will return to the display shown in step 5 and the alarm LED will be OFF.
n
o4-17: Set/Reset Real Time Clock
The time setting screen will appear.
No.
(Addr.
LCD Display
Hex)
Set Time
o4-17
0: — —
(3100)
1: Set
2: Reset
Setting 0: — —
No Setting
Setting 1: Set
The HOA keypad shows the Clock Adjustment display. In Clock Adjustment Mode the user can adjust the Real Time Clock.
Setting 2: Reset
The Real-Time Clock data is cleared. A TIM fault will occur until o4-17 is set to 1 to set the Real Time Clock.
108
Procedure
Name
Sets the current date and time for the Real Time Clock.
Set/Reset Real Time
0: — — No Setting
Clock
1: Real Time Clock Set
2: Real Time Clock Reset
Description
YASKAWA TOEP YAIZ1U 03B YASKAWA AC Drive – Z1000 User Manual
Display
ALM
ALM
- PRMSET - PRG
Initialization
A1-00 = 0
Select Language
FWD
HOME
DATA
ALM
ALM
- PRMSET - PRG
Maintenance
o4-17 = 0
Set time
FWD
HOME
DATA
ALM
ALM
- PRMSET - PRG
Set time
o4-17=
0
*0*
- -
"0"
FWD
HOME
DATA
ALM
ALM
- PRMSET - PRG
Set time
o4-17=
1
*0*
Set
"0"
HOME
FWD
DATA
ALM
ALM
YYYY/MM/DD HH:MM
20
1
0/01/01 00:00
Second per month
+ 0 sec
ALM
Entry accepted
Values
Default: 0
Range: 0 to 2