T1-04: Motor Rated Current
Sets the motor rated current according to the motor nameplate value. Enter the current at the motor base speed.
No.
T1-04
n
T1-05: Motor Base Frequency
Sets the motor rated frequency according to the motor nameplate value. If a motor with an extended speed range is used or
the motor is used in the field weakening area, enter the maximum frequency to E1-04 after Auto-Tuning is complete.
No.
T1-05
n
T1-06: Number of Motor Poles
Sets the number of motor poles according to the motor nameplate value.
No.
T1-06
n
T1-07: Motor Base Speed
Sets the motor rated speed according to the motor nameplate value. Enter the speed at base frequency when using a motor
with an extended speed range or if using the motor in the field weakening area.
No.
T1-07
n
T1-11: Motor Iron Loss
Provides iron loss information to determine the Energy Saving coefficient. T1-11 will first display the value for the motor iron
loss that the drive automatically calculated when the motor capacity was entered to T1-02. Enter the motor iron loss value
listed to T1-11 if the motor test report is available.
No.
T1-11
n
T1-12: T1 Tuning Start
Set T1-12 to 0 to start IM Auto-Tuning.
No.
T1-12
u

T2: Parameter Settings during PM Motor Auto-Tuning

The T2-oo parameters are used to set the Auto-Tuning input data for PM motor tuning.
n
T2-01: PM Motor Auto-Tuning Mode Selection
No.
T2-01
Setting 0: PM Motor Parameter Settings
YASKAWA TOEP YAIZ1U 03B YASKAWA AC Drive – Z1000 User Manual
Name
Motor Rated Current
Name
Motor Base Frequency
Name
Number of Motor Poles
Name
Motor Base Speed
Name
Motor Iron Loss
Name
T1 Tuning Start
Name
PM Motor Auto-Tuning Mode Selection
Setting Range
10.0 to 300.0% of drive rated
current
Setting Range
0.0 to 240.0 Hz
Setting Range
2 to 48
Setting Range
0 to 14400 r/min
Setting Range
0 to 65535 W
Setting Range
0
Setting Range
0
4.8 Auto-Tuning
Default
Determined by
o2-04
Default
60.0 Hz
Default
4
Default
1750 r/min
Default
14 W
Default
4
Default
0