H2: Multi-Function Digital Outputs - YASKAWA A1000 Technical Manual

Hide thumbs Also See for A1000:
Table of Contents

Advertisement

B.7 H Parameters: Multi-Function Terminals
H1-oo
Function
Setting
DriveWorksEZ
90 to 97
digital inputs 1 to 8
9F
DriveWorksEZ disable
u

H2: Multi-Function Digital Outputs

No.
(Addr.
Name
Hex)
H2-01
Terminal M1-M2 function
(40B)
selection (relay)
H2-02
Terminal M3-M4 function
(40C)
selection (relay)
H2-03
Terminal M5-M6 function
(40D)
selection (relay)
H2-06
Watt Hour Output Unit
(437)
Selection
H2-oo
Function
Setting
0
During run
1
Zero speed
2
Speed agree 1
3
User-set speed agree 1
4
Frequency detection 1
5
Frequency detection 2
6
Drive ready
7
DC bus undervoltage
8
During baseblock (N.O.)
9
Frequency reference source
A
Run command source
B
Torque detection 1 (N.O.)
C
Frequency reference loss
D
Braking resistor fault
E
Fault
F
Through mode
10
Minor fault
11
Fault reset command active
12
Timer output
13
Speed agree 2
14
User-set speed agree 2
208
H1 Multi-Function Digital Input Selections
Reserved for DWEZ input functions
Open: DWEZ enabled
Closed: DWEZ disabled
Refer to H2 Multi-Function Digital Output Settings on pages
descriptions of setting values.
Outputs a 200 ms pulse signal when the watt-hour counter increases by the
units selected.
0: 0.1 kWh units
1: 1 kWh units
2: 10 kWh units
3: 100 kWh units
4: 1000 kWh units
H2 Multi-Function Digital Output Settings
Closed: A Run command is active or voltage is output.
Open: Output frequency is above the minimum output frequency set in E1-09.
Closed: Output frequency is below the minimum output frequency set in E1-09.
Closed: Output frequency equals the speed reference (plus or minus the hysteresis set to L4-02).
Closed: Output frequency and speed reference equal L4-01 (plus or minus the hysteresis set to
L4-02).
Closed: Output frequency is less than or equal to the value in L4-01 with hysteresis determined
by L4-02.
Closed: Output frequency is greater than or equal to the value in L4-01 with hysteresis determined
by L4-02.
Closed: Power up is complete and the drive is ready to accept a Run command.
Closed: DC bus voltage is below the Uv trip level set in L2-05.
Closed: Drive has entered the baseblock state (no output voltage).
Open: External Reference 1 or 2 supplies the frequency reference (set in b1-01 or b1-15).
Closed: Digital operator supplies the frequency reference.
Open: External Reference 1 or 2 supplies the Run command (set in b1-02 or b1-16).
Closed: Digital operator supplies the Run command.
Closed: An overtorque or undertorque situation has been detected.
Closed: Analog frequency reference has been lost.
Closed: Braking resistor or transistor is overheated or faulted out.
Note: This function is not available in models CIMR-Ao4A0930 and 4A1200.
Closed: Fault occurred.
Set this value when using the terminal in the pass-through mode.
Closed: An alarm has been triggered, or the IGBTs have reached 90% of their expected life span.
Closed: A command has been entered to clear a fault via the input terminals or from the serial
network.
Closed: Timer output.
Closed: When drive output frequency equals the frequency reference ±L4-04.
Closed: When the drive output frequency is equal to the value in L4-03 ±L4-04.
YASKAWA ELECTRIC TOEP C710616 41B YASKAWA AC Drive - A1000 Quick Start Guide
Description
Description
208
Description
Values
to
209
for
Default: 0
Range: 0 to 192
Default: 1
Range: 0 to 192
Default: 2
Range: 0 to 192
Default: 0
Range: 0 to 4
Page
Page
105
105
105
Page
106
106