YASKAWA Z1000 User Manual page 167

Ac drive for hvac fan and pump
Hide thumbs Also See for Z1000:
Table of Contents

Advertisement

Note:
1. The drive will use the active accel/decel time to pass through the specified dead band range, but will not allow continuous operation in
that range.
2. When setting more than one Jump frequency, make sure that d3-01≥ d3-02 ≥ d3-03.
n
E1-03: V/f Pattern Selection
Selects the V/f pattern for the drive and motor from 15 predefined patterns or creates a custom V/f pattern.
No.
E1-03
<1> Settings 0 through E are not available in OLV/PM (A1-02 = 5).
<2> Parameter is not reset to the default value when the drive is initialized using A1-03.
Setting a Predefined V/f Pattern (Setting 0 to F)
Choose the V/f pattern that best meets the application demands from the table below. These settings are available only in
V/f Control modes. Set the correct value to E1-03. Parameters E1-04 to E1-13 can only be monitored, not changed.
Note:
1. Setting an improper V/f pattern may result in low motor torque or increased current due to overexcitation.
2. Drive initialization does not reset parameter E1-03.
Setting
Specification
0
50 Hz
1
60 Hz
2
60 Hz (with 50 Hz base)
3
72 Hz (with 60 Hz base)
4
50 Hz, Variable torque 1
5
50 Hz, Variable torque 2
6
50 Hz, Variable torque 3
7
50 Hz, Variable torque 4
8
50 Hz, Mid starting torque
9
50 Hz, High starting torque
A
60 Hz, Mid starting torque
B
60 Hz, High starting torque
C
90 Hz (with 60 Hz base)
D
120 Hz (with 60 Hz base)
E
180 Hz (with 60 Hz base)
YASKAWA TOEP YAIZ1U 03B YASKAWA AC Drive – Z1000 User Manual
Frequency
Reference
Frequency
reference
decreases
Frequency
Width (d3-04)
Jump
Frequency 3
d3-03
Figure 4.33 Jump Frequency Operation
Parameter Name
V/f Pattern Selection
Table 4.25 Predefined V/f Patterns
Characteristic
Constant torque
Variable torque
High starting torque
Constant output
4.13 Advanced Drive Setup Adjustments
Frequency
reference
increases
Jump
Frequency
Width (d3-04)
Jump
Frequency
Width (d3-04)
Jump
Jump
Jump
Frequency 2
Frequency 1
d3-02
d3-01
Setting Range
For general purpose applications. Torque remains constant
regardless of changes to speed.
For fans, pumps, and other applications where the required
torque changes as a function of the speed.
Select high starting torque when:
• Wiring between the drive and motor exceeds 150 m.
• A large amount of starting torque is required.
• An AC reactor is installed.
Output voltage is constant when operating at greater than
60 Hz.
Output
Frequency
Default
<1>
0 to F
F
Application
<2>
4
167

Advertisement

Table of Contents
loading

Table of Contents