U4: Maintenance Monitors - YASKAWA Z1000 User Manual

Ac drive for hvac fan and pump
Hide thumbs Also See for Z1000:
Table of Contents

Advertisement

u

U4: Maintenance Monitors

No.
(Addr.
Name
Hex)
U4-01
Cumulative Operation
(4C)
Time
U4-02
Number of Run
(75)
Commands
U4-03
Cooling Fan Operation
(67)
Time
U4-04
Cooling Fan
(7E)
Maintenance
U4-05
Capacitor Maintenance
(7C)
U4-06
Soft Charge Bypass
(7D6)
Relay Maintenance
U4-08
Heatsink Temperature
(68)
U4-09
LED Check
(5E)
U4-10
kWh, Lower 4 Digits
(5C)
U4-11
kWh, Upper 5 Digits
(5D)
U4-13
Peak Hold Current
(7CF)
U4-14
Peak Hold Output
(7D0)
Frequency
U4-16
Motor Overload
(7D8)
Estimate (oL1)
U4-18
Frequency Reference
(7DA)
Source Selection
Frequency Reference
U4-19
from MEMOBUS/
(7DB)
Modbus Comm.
U4-20
Option Frequency
(7DC)
Reference
YASKAWA TOEP YAIZ1U 03B YASKAWA AC Drive – Z1000 User Manual
LCD Display
Displays the cumulative operation time of the drive. The value
for the cumulative operation time counter can be reset in
parameter o4-01. Use parameter o4-02 to determine if the
Drv Elapsed Time
operation time should start as soon as the power is switched on
or only while the Run command is present. The maximum
number displayed is 99999, after which the value is reset to 0.
Displays the number of times the Run command is entered. Reset
RUN Cmd Counter
the number of Run commands using parameter o4-13. This value
will reset to 0 and start counting again after reaching 65535.
Displays the cumulative operation time of the cooling fan. The
default value for the fan operation time is reset in parameter
Fan Elapsed TIme
o4-03. This value will reset to 0 and start counting again after
reaching 99999.
Displays main cooling fan usage time as a percentage of its
Fan Life Mon
expected performance life. Parameter o4-03 can be used to reset
this monitor.
Displays main circuit capacitor usage time as a percentage of their
Cap Life Mon
expected performance life. Parameter o4-05 can be used to reset
this monitor.
Displays the soft charge bypass relay maintenance time as a
ChgCirc Life Mon
percentage of its estimated performance life. Parameter o4-07 can
be used to reset this monitor.
Displays the heatsink temperature.
Heatsink Temp
Lights all segments of the LED to verify that the display is
LED Oper Check
working properly.
Monitors the drive output power. The value is shown as a 9-digit
kWh Lower 4 dig
number displayed across two monitor parameters, U4-10 and
U4-11.
Example:
12345678.9 kWh is displayed as:
kWh Upper 5 dig
U4-10: 678.9 kWh
U4-11: 12345 MWh
Displays the highest current value that occurred during run.
Current PeakHold
Displays the output frequency when the current value shown in
Freq@ I PeakHold
U4-13 occurred.
Shows the value of the motor overload detection accumulator.
Motor OL1 Level
100% is equal to the oL1 detection level.
Displays the source for the frequency reference as XY-nn.
X: indicates which reference is used:
0 = OFF
1 = AUTO
2 = HAND
Y-nn: indicates the reference source
0-01 = HOA keypad
Reference Source
1-00 = Analog (not assigned)
1-01 = Analog (terminal A1)
1-02 = Analog (terminal A2)
2-02 to 17 = Multi-step speed (d1-02 to 17)
3-01 = MEMOBUS/Modbus communications
4-01 = Communication option card
9-01 = Up/Down
Displays the frequency reference provided by MEMOBUS/
MEMOBUS Freq Ref
Modbus (decimal).
Displays the frequency reference input by an option card
Option Freq Ref
(decimal).
Description
B.13 U: Monitors
Analog
Unit
Output Level
No signal output
1 h
available
No signal output
1 Time
available
No signal output
1 h
available
No signal output
1%
available
No signal output
1%
available
No signal output
1%
available
10 V: 100 °C
1 °C
No signal output
available
No signal output
1 kWh
available
No signal output
1 MWh
available
No signal output
0.01 A
available
<1>
No signal output
0.01 Hz
available
10 V: 100%
0.1%
No signal output
available
No signal output
0.01%
available
B
No signal output
available
321