4.13 Advanced Drive Setup Adjustments
No.
A1-00
A1-02
E1-03
F6-08
L8-35
o2-04
n
A1-06: Application Preset
Several Application Presets are available to facilitate drive setup for commonly used applications. Selecting one of these
Application Presets automatically assigns functions to the input and output terminals and sets a predefined group of parameters
to values appropriate for the selected application.
In addition, the parameters most likely to be changed are assigned to the group of User Parameters, A2-01 through A2-16.
User Parameters are part of the Setup Group, which provides quicker access by eliminating the need to scroll through multiple
menus.
n
b1-04: Reverse Operation Selection
Enables and disables Reverse operation. For some applications, reverse motor rotation is not appropriate and may cause
problems (e.g., air handling units, pumps, etc.).
No.
b1-04
Setting 0: Reverse Enabled
Possible to operate the motor in both forward and reverse directions.
Setting 1: Reverse Disabled
Drive disregards a Reverse run command or a negative frequency reference.
n
b1-14: Phase Order Selection
Sets the phase order for drive output terminals U/T1, V/T2, and W/T3.
Switching motor phases will reverse the direction of the motor.
No.
b1-14
Setting 0: Standard
Setting 1: Switch Phase Order
The direction of the motor is reversed.
n
b1-17: Run Command at Power Up
Determines whether an external Run command that is active during power up will start the drive.
No.
b1-17
Setting 0: Disregarded
A new Run command must be issued after power up. Cycle the Run command to start the drive.
Note:
For safety reasons, the drive is initially programmed not to accept a Run command at power up (b1-17 = 0). If a Run command is issued at
power up, the AUTO LED will flash quickly.
Setting 1: Allowed
The motor will start immediately after a power up if a Run command is already enabled.
152
Table 4.23 Parameters Not Changed by Drive Initialization
Parameter Name
Reverse Operation Selection
Parameter Name
Phase Order Selection
Parameter Name
Run Command at Power Up
Parameter Name
Language Selection
Control Method Selection
V/f Pattern Selection
Communication Parameter Reset
Installation Selection
Drive Model Selection
Setting Range
Setting Range
Setting Range
YASKAWA TOEP YAIZ1U 03B YASKAWA AC Drive – Z1000 User Manual
Default
0, 1
1
Default
0, 1
0
Default
0, 1
1

Advertisement

Table of Contents
loading

Table of Contents