H2: Multi-Function Digital Outputs - YASKAWA T1000A Technical Manual

Table of Contents

Advertisement

5.7 H: Terminal Functions
Setting 71: Speed/Torque Control switch
Switches the drive between Torque Control and Speed Control. Torque Control is enabled when the terminal is closed,
and Speed Control is enabled when the terminal is open. Note that parameter d5-01 must be set to 0 when using this
function. See
d5: Torque Control on page 158
Setting 72: Zero Servo
Used to activate the Zero Servo function that can be used to lock the rotor at a certain position. Refer to
on page 139
for details.
Setting 77: ASR gain switch
Switches the ASR gain between the values set to C5-01 and C5-03. The gain set to C5-03 is enabled when the terminal is
closed, and C5-01 is enabled when the terminal opens again. See
1, 2 / ASR Integral Time 1, 2 on page 148
Setting 78: External torque reference polarity inversion
Reverses the direction of the torque reference when the terminal closes. Refer to
Setting the Torque Reference, Speed Limit, and Torque Compensation Values on page 158
Setting 7C, 7D: Short Circuit Braking (N.O., N.C.) (OLV/PM, AOLV/PM)
An input programmed for this function can be used to activate Short Circuit Braking in Open Loop Vector control modes
for PM motors. By linking all three phases of a PM motor, Short Circuit Braking creates a braking torque that can be used
to stop a rotating motor or prevent a motor from coasting due to external forces. Parameter b2-18 can be used to limit the
current during Short Circuit Braking.
DIgital Input Function
Setting 7C (N.O.)
Setting 7D (N.C.)
Setting 7E: Forward/reverse detection (for V/f Control with Simple PG Feedback)
When a digital input is programmed for this function, the input determines the motor rotation direction for V/f Control
with Simple PG feedback (A1-02 = 0 and H6-01 = 3). If the input is open, the speed feedback signal is considered to be
forward. If the input is closed, it is considered to be in reverse.
u H2: Multi-Function Digital Outputs
n
H2-01 to H2-03: Terminal M1-M2, M3-M4, and M5-M6 Function Selection
The drive has three multi-function output terminals.
H2-01, H2-02, and H2-03.
No.
H2-01
H2-02
H2-03
Setting
0
During run
1
Zero Speed
2
Speed agree 1
3
User-set speed agree 1
4
Frequency detection 1
5
Frequency detection 2
6
Drive ready
7
DC bus undervoltage
8
During baseblock (N.O.)
9
Frequency reference source
A
Run command source
B
Torque detection 1 (N.O.)
C
Frequency reference loss
190
and
for a more detailed description.
Parameter Name
Terminal M1-M2 Function Selection
Terminal M3-M4 Function Selection
Terminal M5-M6 Function Selection
Table 5.22 Multi-Function Digital Output Terminal Settings
Function
Page
Switching Between Torque and Speed Control on page
C5-01, C5-03 / C5-02, C5-04: ASR Proportional Gain
Drive Operation
Input Open
Normal operation
Short-Circuit Braking
Refer to H6: Pulse Train Input/Output on page
Table 5.22
lists the functions available for theses terminals using
Setting
191
1C
Motor 2 selection
191
1D
During regeneration
191
1E
Restart enabled
192
1F
Motor overload alarm (oL1)
192
20
Drive overheat pre-alarm (oH)
193
2F
Maintenance period
193
30
During torque limit
193
31
During speed limit
193
32
During speed limit in Torque Control
194
33
Zero Servo complete
194
37
During frequency output
194
38
Drive enabled
194
39
Watt hour pulse output
YASKAWA ELECTRIC SIEP C710616 30B YASKAWA AC Drive T1000A Technical Manual
d5: Torque Control on page 158
for details.
Input Closed
Short Circuit Braking
Normal operation
Setting Range
0 to 161
0: During run
0 to 161
1: Zero Speed
0 to 161
2: Speed agree 1
Function
160.
b9: Zero Servo
and
208.
Default
Page
197
197
197
197
197
197
198
198
198
198
198
198
198