T2-12: PM Motor q-Axis Inductance
Enter the q-Axis inductance per motor phase.
No.
T2-12
n
T2-13: Induced Voltage Constant Unit Selection
Selects the units used for setting the induced voltage coefficient.
No.
T2-13
Setting 0: mV (r/min)
Setting 1: mV (rad/sec)
Note:
If T2-13 is set to 0, then the drive will use E5-24 (Motor Induction Voltage Constant 2), and will automatically set E5-09 (Motor Induction
Voltage Constant 1 (Ke)) to 0.0. If T2-13 is set to 1, then the drive will use E5-09 and will automatically set E5-25 to 0.0.
n
T2-14: PM Motor Induced Voltage Constant (Ke)
Enter the motor induced voltage constant (Ke).
No.
T2-14
n
T2-15: Pull-In Current Level for PM Motor Tuning
Sets the amount of pull-in current. Set as a percentage of the motor rated current.
No.
T2-15
Pull-In Current Level for PM Motor Tuning
n
T2-18: T2 Tuning Start
Set T2-18 to 0 to start PM motor Auto-Tuning.
No.
T2-18
YASKAWA TOEP YAIZ1U 03B YASKAWA AC Drive – Z1000 User Manual
Name
PM Motor q-Axis Inductance
Name
Induced Voltage Constant Unit Selection
Name
PM Motor Induced Voltage Constant (Ke)
Name
Name
T2 Tuning Start
4.8 Auto-Tuning
Setting Range
0.00 to 600.00 mH
Determined by T2-02
Setting Range
0, 1
Setting Range
0.0 to 2000.0
Determined by T2-02
Setting Range
0 to 120%
Setting Range
0
Default
Default
0
Default
Default
30%
Default
4