YASKAWA Z1000 User Manual page 351

Ac drive for hvac fan and pump
Hide thumbs Also See for Z1000:
Table of Contents

Advertisement

Drive Model
5A0145
5A0192
5A0242
n
Grounding
The drive is designed to be used in T-N (grounded neutral point) networks. If installing the drive in other types of grounded
systems, contact your Yaskawa representative for instructions.
n
CE Standards Compliance for DC Power Supply Input
Install the fuses in the following tables to meet CE standards.
Figure D.2 Example of DC Power Supply Input (Two Drives Connected in Series)
Note:
1. When connecting multiple drives together, make sure that each drive has its own fuse. Replace all fuses when one fuse blows.
2.
Refer to Standard Connection Diagram on page 70
3. The recommended fuses and fuse holders are made by Fuji Electric.
n
Guarding Against Harmful Materials
When installing IP00/Open Type enclosure drives, use an enclosure that prevents foreign material from entering the drive
from above or below.
YASKAWA TOEP YAIZ1U 03B YASKAWA AC Drive – Z1000 User Manual
Manufacturer: Bussmann
Model
FWP-350A
FWP-600A
FWP-600A
DC power supply
(converter)
Fuse
+
+1
_
_
Drive
Fuse
+1
_
Drive
for an AC power supply.
D.2 European Standards
Fuse Type
Fuse Ampere Rating (A)
350
600
600
U/ T1
M
V/ T2
W/ T3
U/ T1
M
V/ T2
W/ T3
D
351