5.4 Fault Detection
Digital Operator Display
Cause
The node setup terminal closed during run.
A Run command was issued while the node
setup function was active.
Digital Operator Display
Cause
The motor has been damaged due to
overheating or the motor insulation is
damaged
One of the motor cables has shorted out or
there is a grounding problem
The load is too heavy
The acceleration or deceleration times are too
short
The drive is attempting to operate a specialized
motor or a motor larger than the maximum size
allowed
Magnetic contactor (MC) on the output side of
the drive has turned on or off
V/f setting is not operating as expected
Excessive torque compensation
Drive fails to operate properly due to noise
interference
Overexcitation gain is set too high
Run command was applied while motor was
coasting
The rated output current of the drive is too
small
Digital Operator Display
Cause
The option card installed into port CN5-A is
incompatible with the drive
206
Node Setup Error
nSE
A terminal assigned to the node setup function closed during run.
Stop the drive when using the node setup function.
Overcurrent
oC
Drive sensors detected an output current greater than the specified overcurrent level.
• Check the insulation resistance.
• Replace the motor.
• Check the motor cables.
• Remove the short circuit and reapply power to the drive.
• Check the resistance between the motor cables and the ground terminal
• Replace damaged cables.
• Measure the current flowing into the motor.
• Replace the drive with a larger capacity drive if the current value exceeds the rated current.
• Determine if there is sudden fluctuation in the current level.
• Reduce the load to avoid sudden changes in the current level or switch to a larger drive.
Calculate the torque needed during acceleration relative to the load inertia and the specified acceleration
time. If it is not possible to set the proper amount of torque, make the following changes:
• Increase the acceleration time (C1-01, C1-03).
• Increase the S-curve characteristics (C2-01 through C2-04).
• Increase the capacity of the drive.
• Check the motor capacity.
• Ensure that the rated capacity of the drive is greater than or equal to the capacity rating found on the
motor nameplate.
Set up the operation sequence so the MC does not trip while the drive is outputting current.
• Check the ratios between the voltage and frequency.
• Set parameters E1-04 through E1-10 appropriately.
• Lower the voltage if it is too high relative to the frequency.
• Check the amount of torque compensation.
• Reduce the torque compensation gain (C4-01) until there is no speed loss and less current.
• Review the possible solutions provided for handling noise interference.
• Review the section on handling noise interference on page
circuit lines, and ground wiring.
• Review the section on handling noise interference and check the control circuit lines, main circuit lines,
and ground wiring.
• Check if the fault occurs simultaneously with overexcitation function operation.
• Consider motor flux saturation and reduce the value of n3-13 (Overexcitation Deceleration Gain).
• Set b3-01 to 1 to enable Speed Search at Start.
• Program the Speed Search command input through one of the multi-function contact input terminals
(H1-oo = 61 or 62).
Use a larger drive.
Option Card Connection Error at Option Port CN5-A
oFA00
Option compatibility error
Check if the drive supports the option card to be installed. Contact Yaskawa for assistance.
Fault Name
Possible Solution
Fault Name
Possible Solution
240
and check the control circuit lines, main
Fault Name
Possible Solution
YASKAWA TOEP YAIZ1U 03B YASKAWA AC Drive – Z1000 User Manual
.