YASKAWA Z1000 User Manual page 71

Ac drive for hvac fan and pump
Hide thumbs Also See for Z1000:
Table of Contents

Advertisement

Terminals , 1, 2, B1, B2 are
for connection options. Never
connect power supply lines to
these terminals
Main
Fuse
Switch
Three-Phase
R
Power Supply
S
600 V
T
50/60 Hz
Forward Run / Stop
Reverse Run / Stop
External fault
Fault reset
Multi-function
Multi-speed step 1
digtial inputs
(default setting)
Multi-speed step 2
Jog speed
Factory installed wire link
Sink / Source mode
selection
(default: Sink)
2 k
Multi-function
analog inputs
MEMOBUS/Modbus Communication
RS-422/RS-485 Maximum 115.2 kbps
BACnet Communication
Apogee FLN, Siemens
Metasys N2, Johnson Controls
+24 Vdc
External
Supply
(max. 150 mA)
<1> Remove the jumper when installing a DC link choke. Models 5A0041 to 5A0242 come with a built-in DC link choke.
<2> Set L8-55 to 0 to disable the protection function of the built-in braking transistor of the drive when using an optional regenerative
converter or dynamic braking option. Leaving L8-55 enabled may cause a braking resistor fault (rF). Additionally, disable Stall
Prevention (L3-04 = 0) when using an optional regenerative converter, regenerative or braking units, or dynamic braking option.
Leaving If L3-04 enabled may prevent the drive from stopping within the specified deceleration time.
<3> Supplying power to the control circuit separately from the main circuit requires 24 V power supply (option).
YASKAWA TOEP YAIZ1U 03B YASKAWA AC Drive – Z1000 User Manual
DC link choke
(option)
U
U
Jumper
+ +
+
+
2
Main Circuit
R/L1
EMC
S/L2
Z1000 Drive (600 V)
Filter
T/L3
Control Circuit
S 1
S 2
S 3
S 4
S 5
S 6
S 7
SN
SC
SP
<4>
+
24 V
<5>
FE
Shield ground terminal
<6>
+
V
Power supply +10.5 Vdc, max. 20 mA
A 1
Analog Input 1 (Frequency Reference Bias)
0 to +10 Vdc (20 kΩ) Resolution: Unsigned 12 bit
4 to 20 mA (250 Ω) / 0 to 20 mA (250 Ω)
A 2
Analog Input 2 (Frequency Reference Bias)
0 to +10 Vdc (20 kΩ) Resolution: Unsigned 12 bit
4 to 20 mA (250 Ω) / 0 to 20 mA (250 Ω)
AC
Termination resistor
(120 , 1/2 W)
0 V
DIP
Switch S2
+
+
R
-
-
R
+
+
S
S -
IG
+
+P
External power supply
24 Vdc, max. 150 ma
SN
twisted-pair shielded line
shielded line
Figure 3.1 Drive Standard Connection Diagram
<1>
X
X
Braking resistor
(option)
<2>
1
B 1
B 2
<3>
Option board
connectors
CN5-C
CN5-B
CN5-A
Terminal board
jumpers and switches
DIP Switch S2
Off
On
Term. Res. On/Off
Jumper S1
V
A1/A2 Voltage/Current
I
Selection
A1 A2
Jumper S5
V
AM/FM Voltage/Current
Selection
I
FM
AM
<7>
<8>
<10>
0 V
control circuit terminal
3.2 Standard Connection Diagram
<11>
FU
FV
M
FW
Cooling fan
U
U/T 1
V
V/T 2
M
W
W/T
3
Ground
MA
Fault output
MB
250 Vac, max. 1 A
30 Vdc, max 1 A
MC
(min. 5 Vdc, 10 mA)
M 1
Multi-function relay output (During Run)
250 Vac, max. 1 A
M 2
30 Vdc, max 1 A
(min. 5 Vdc, 10 mA)
M 3
Multi-function relay output (Zero Speed)
250 Vac, max. 1 A
M 4
30 Vdc, max 1 A
(min. 5 Vdc, 10 mA)
M 5
Multi-function relay output (Speed Agree 1)
250 Vac, max. 1 A
M 6
30 Vdc, max 1 A
(min. 5 Vdc, 10 mA)
Multi-function analog output 1
FM
(Output frequency)
+
FM
-10 to +10 or 0 to +10 Vdc (2 mA)
or 4 to 20 mA
AM
Multi-function analog output 2
+
AC
(Output current)
AM
-10 to +10 or 0 to +10 Vdc (2 mA)
<9>
or 4 to 20 mA
E (G)
main circuit terminal
3
<9>
71