D.3 UL and CSA Standards
Terminal
Wire Gauge
Screws
M10
4/0 AWG × 2P
4/0 AWG × 4P
M12
M10
250 / 300 kcmil
M12
250 kcmil × 2P
M10
250 kcmil × 4P
300 kcmil × 2P
M12
300 kcmil × 4P
M10
350 kcmil
400 kcmil
M12
<1> Codes refer to a set of three crimp terminals and three insulation caps. Prepare input and output wiring using two sets for each connection.
Example 1: Models with 300 kcmil for both input and output require one set for input terminals and one set for output terminals, so the user should
order two sets of [100-051-272].
Example 2: Models with 4/0 AWG × 2P for both input and output require two sets for input terminals and two sets for output terminals, so the user
should order four sets of [100-051-560].
Note:
Use crimp insulated terminals or insulated shrink tubing for wiring connections. Wires should have a continuous maximum allowable
temperature of 75 °C 600 Vac UL-approved vinyl-sheathed insulation.
Factory Recommended Branch Circuit Protection for UL Compliance
NOTICE: If a fuse is blown or a Ground Fault Circuit Interrupter (GFCI) is tripped, check the wiring and the selection of the peripheral devices.
Check the wiring and the selection of peripheral devices to identify the cause. Contact Yaskawa before restarting the drive or the peripheral
devices if the cause cannot be identified.
Yaskawa recommends installing one of the following types of branch circuit protection to maintain compliance with UL508C.
Semiconductor protective type fuses are preferred. Alternate branch circuit protection devices are also listed in
Nominal
Drive Model
Output Power
5A0003
5A0004
5A0006
5A0009
5A0011
5A0017
5A0022
5A0027
5A0032
5A0041
5A0052
5A0062
5A0077
5A0099
5A0125
5A0145
5A0192
5A0242
<1> Maximum MCCB Rating is 15 A, or 200 % of drive input current rating, whichever is larger. MCCB voltage rating must be 600 VAC or greater.
<2> Maximum Time Delay fuse is 175% of drive input current rating. This covers any Class CC, J or T class fuse.
<3> Maximum Non-time Delay fuse is 300% of drive input current rating. This covers any CC, J or T class fuse.
<4> When using semiconductor fuses, Bussman FWP are required for UL compliance.
<5> Class L fuse is also approved for this rating.
356
Crimp Terminal
Model Number
100-L10
100-L12
R150-10
R150-12
150-L10
150-L12
200-10
R200-12
Table D.4 Factory Recommended Drive Branch Circuit Protection
AC Drive Input
Amps
HP
2
3.6
3
5.1
5
8.3
7.5
12
10
16
15
23
20
31
25
38
30
45
40
44
50
54
60
66
75
80
100
108
125
129
150
158
200
228
250
263
Tool
Machine No.
YF-1, YET-150-1
TD-228, TD-214
YF-1, YET-300-1
TD-324, TD-312
YF-1. YET-150-1
TD-229, TD-215
YF-1, YET-300-1
TD-325, TD-313
YF-1, YET-150-1
TD-229, TD-215
YF-1, YET-300-1
TD-325, TD-313
YF-1, YET-300-1
TD-327, TD-314
YF-1, YET-300-1
TD-327, TD-314
MCCB Rating
Time Delay Fuse
Amps
Rating Amps
<1>
600 V Class
15
15
15
20
30
40
60
75
75
75
100
125
150
175
225
300
400
500
YASKAWA TOEP YAIZ1U 03B YASKAWA AC Drive – Z1000 User Manual
Insulation
Cap
Die Jaw
Model No.
TP-100
TP-100
TP-150
TP-150
TP-150
TP-150
TP-200
TP-200
Non-time Delay
Fuse Rating
<2>
<3>
Amps
6.25
10
8
15
12
20
20
35
25
45
40
60
50
90
60
110
75
125
75
125
90
150
110
175
125
225
175
300
225
350
275
450
350
600
450
700
<1>
Code
100-051-559
100-051-560
100-051-272
100-051-273
100-051-561
100-051-562
100-051-563
100-051-275
Table
6.3.
Bussmann Semi-
conductor Fuse
Rating (Fuse
<4>
Ampere)
FWP-50B (50)
FWP-50B (50)
FWP-60B (60)
FWP-60B (60)
FWP-70B (70)
FWP-100B (100)
FWP-100B (100)
FWP-125A (125)
FWP-125A (125)
FWP-175A (175)
FWP-175A (175)
FWP-250A (250)
FWP-250A (250)
FWP-250A (250)
FWP-350A (350)
FWP-350A (350)
FWP-600A (600)
FWP-600A (600)