YASKAWA Z1000 User Manual page 275

Ac drive for hvac fan and pump
Hide thumbs Also See for Z1000:
Table of Contents

Advertisement

No.
(Addr.
Name
Hex)
b5-10
PI Output Gain Setting Output Gain
(1AE)
b5-11
PI Output Reverse
(1AF)
Selection
b5-12
PI Feedback Loss
(1B0)
Detection Selection
b5-13
PI Feedback Loss
(1B1)
Detection Level
b5-14
PI Feedback Loss
(1B2)
Detection Time
b5-15
PI Sleep Function Start
(1B3)
Level
b5-16
PI Sleep Delay Time
(1B4)
b5-17
PI Accel/Decel Time
(1B5)
b5-18
PI Setpoint Selection
(1DC)
b5-19
(1DD)
PI Setpoint Value
b5-20
PI Setpoint Scaling
(1E2)
b5-21
PI Sleep Input Source
(1E3)
b5-22
PI Snooze Level
(1E4)
b5-23
PI Snooze Delay Time
(1E5)
b5-24
PI Snooze Deactivation
(1E6)
Level
b5-25
PI Setpoint Boost
(1E7)
Setting
YASKAWA TOEP YAIZ1U 03B YASKAWA AC Drive – Z1000 User Manual
LCD Display
Sets the gain applied to the PI output.
0: Negative PI output triggers zero limit.
Output Rev Sel
1: Rotation direction reverses with negative PI output.
0: 0 limit
Note:
1: Reverse
0: Digital Output Only
(Remains active when PI is disabled by digital input)
Fb loss Det Sel
1: Alarm output, drive continues operation (Remains active
0: DO Only - Always
when PI is disabled by digital input)
1: Alarm - Always
2: Fault output, drive output is shut off (Remains active when
2: Fault - Always
PI is disabled by digital input)
3: DO Only@PID
3: Digital output only. No detection when PI is disabled by
Enbl
digital input.
4: Alarm @ PID Enbl
4: Alarm detection. No detection when PI is disabled by digital
5: Fault @ PID Enbl
input.
5: Fault detection. No detection when PI is disabled by digital
input.
Sets the PI feedback loss detection level as a percentage of the
Fb loss Det Lvl
maximum output frequency.
Sets a delay time for PI feedback loss.
Fb loss Det Time
Sets the frequency level that triggers the sleep/snooze function. Default:
PID Sleep Level
Sets a delay time before the sleep/snooze function is triggered. Default: 0.0 s
PID Sleep Time
Sets the acceleration and deceleration time to PI setpoint.
PID Acc/Dec Time
PID Setpoint Sel
0: Disabled
0: Disabled
1: Enabled
1: Enabled
Sets the PI target value when b5-18 = 1. Set as a percentage of
the maximum output frequency.
PID Setpoint
PID Disp Scaling
0: 0.01 Hz units
0: 0.01Hz units
1: 0.01% units (100% = max output frequency)
1: 0.01% units
2: r/min (number of motor poles must entered)
2: r/min
3: User-set (set scaling to b5-38 and b5-39)
3: User Units
PI Sleep Ref
Input source selection for Sleep Function mode.
0: PI Setpoint
0: PI Setpoint
1: Frequency Ref
1: SFS Input
2: Snooze Func
2: Snooze
Sets the PI Snooze Function start level as a percentage of the
Snooze Level
maximum frequency.
Sets the PI Snooze Function delay time in seconds.
Snooze DelayTime
When the PI feedback level drops below this level, the drive
SnoozeRestartLvl
returns to normal operation. Set as a percentage of the maximum
frequency.
Temporarily increases the PI setpoint to create an overshoot of
SetpointBoostLvl
the intended PI setpoint.
Description
When using setting 1, make sure reverse
operation is permitted by b1-04.
B.2 b: Application
Values
Page
Default: 1.00
Min.: 0.00
157
Max.: 25.00
Default: 0
157
Range: 0, 1
Default: 0
158
Range: 0 to 5
Default: 0%
Min.: 0
158
Max.: 100
Default: 1.0 s
Min.: 0.0
159
Max.: 25.5
<1>
159
Min.: 0.0 Hz
Max.: 240.0 Hz
Min.: 0.0
159
Max.: 25.5
Default: 0.0 s
Min.: 0.0
159
Max.: 6000.0
Default: 0
159
Range: 0, 1
Default: 0.00%
Min.: 0.00
159
<2>
Max.: 600.00
Default: 1
160
Range: 0 to 3
Default: 1
160
Range: 0 to 2
Default: 0%
Min.: 0
160
Max.: 100
Default: 0s
Min.: 0
160
Max.: 2600
Default: 0%
Min.: 0
160
B
Max.: 100
Default: 0%
Min.: 0
160
Max.: 100
275