B.7 H Parameters: Multi-Function Terminals
H1-oo
Function
Setting
F
Through mode
10
Up command
11
Down command
12
Forward Jog
13
Reverse Jog
14
Fault reset
15
Fast Stop (N.O.)
17
Fast Stop (N.C.)
18
Timer function input
19
PI disable
1B
Program lockout
1E
Reference sample hold
20 to 2F External fault
30
PI integral reset
31
PI integral hold
34
PI soft starter cancel
35
PI input level selection
290
H1 Multi-Function Digital Input Selections
LCD Display
Select this setting when using the terminal in a pass-through mode. The terminal
Term Not Used
does not trigger a drive function, but it can be used as digital input for the controller
to which the drive is connected.
The drive accelerates when the Up command terminal closes, and decelerates when
the Down command closes. When both terminals are closed or both are open, the
Up Command 1
drive holds the frequency reference. The Up and Down commands must always
be used in conjunction with one another.
The drive accelerates when the Up command terminal closes, and decelerates when
the Down command closes. When both terminals are closed or both are open, the
Down Command 1
drive holds the frequency reference. The Up and Down commands must always
be used in conjunction with one another.
Forward Jog
Closed: Runs forward at the Jog frequency d1-17.
Reverse Jog
Closed: Runs reverse at the Jog frequency d1-17.
Fault Reset
Closed: Resets faults if the cause is cleared and the Run command is removed.
Fast-Stop N.O.
Closed: Decelerates at the Fast Stop time set to C1-09.
Fast-Stop N.C.
Open: Decelerates to stop at the Fast Stop time set to C1-09.
Triggers the timer set up by parameters b4-01 and b4-02. Must be set in conjunction
Timer function
with the timer function output (H2-oo = 12).
Open: PI control enabled
PID Disable
Closed: PI control disabled
Open: Parameters cannot be edited (except for U1-01 if the reference source is
Program Lockout
assigned to the HOA keypad).
Closed: Parameters can be edited and saved.
Closed: Samples the analog frequency reference and operates the drive at that
Ref Sample Hold
speed.
External fault
20: NO/Always Det,
Ramp to Stop
21: NC/Always Det,
Ramp to Stop
22: NO/During RUN,
Ramp to Stop
23: N.C., During run,
ramp to stop
20: N.O., Always detected, ramp to stop
24: NO/ Always Det,
21: N.C., Always detected, ramp to stop
Coast to Stop
22: N.O., During run, ramp to stop
25: NC/Always Det,
23: N.C., During run, ramp to stop
Coast to Stop
24: N.O., Always detected, coast to stop
26: NO/During RUN,
25: N.C., Always detected, coast to stop
Coast to Stop
26: N.O., During run, coast to stop
27: NC/During RUN,
27: N.C., During run, coast to stop
Coast to Stop
28: N.O., Always detected, Fast Stop
28: NO/Always Det,
29: N.C., Always detected, Fast Stop
Fast-Stop
2A: N.O., During run, Fast Stop
29: NC/Always Det,
2B: N.C., During run, Fast Stop
Fast-Stop
2C: N.O., Always detected, alarm only (continue running)
2A: NO/During RUN,
2D: N.C., Always detected, alarm only (continue running)
Fast-Stop
2E: N.O., During run, alarm only (continue running)
2B: NC/During RUN,
2F: N.C., During run, alarm only (continue running)
Fast- Stop
2C: NO/Always Det,
Alarm Only
2D: NC/Always Det,
Alarm Only
2E: NO/ During RUN,
Alarm Only
2F: NC/During RUN,
Alarm Only
PID Intgrl Reset
Closed: Resets the PI control integral value.
Open: Performs integral operation.
PID Intgrl Hold
Closed: Maintains the current PI control integral value.
Open: PI soft starter is enabled.
PID SFS Cancel
Closed: Disables the PI soft starter b5-17.
PID Input Invert
Closed: Inverts the PI input signal.