C.4 BACnet Setup Parameters
C.4 BACnet Setup Parameters
u

BACnet Serial Communication

This section describes parameters necessary to set up BACnet communications.
n
H5-01: Drive Slave Address
Sets the drive slave address used for communications.
Note:
Cycle power for the setting to take effect.
No.
H5-01
Each slave drive must be assigned a unique slave address for serial communications to work. Slave addresses do not need to
be assigned in sequential order, but no two drives may share the same address.
n
H5-02: Communication Speed Selection
Sets the communications speed for APOGEE FLN, BACnet, MEMOBUS/Modbus, and Metasys N2.
Note:
1. Cycle power for the setting to take effect.
2. When Metasys N2 communications are selected (H5-08 = 1), selecting a baud rate other than 9600 bps will trigger an oPE29 error.
3. When APOGEE FLN (P1) communications are selected (H5-08 = 2), selecting a baud rate other than 4800 bps will trigger an oPE29
error.
4. When BACnet communications are selected (H5-08 = 3), selecting 115200 bps (Setting 8) will trigger an oPE29 error.
No.
H5-02
<1> Default depends on H5-08 setting:
H5-08 = 0, MEMOBUS/Modbus; default: 3
H5-08 = 1, N2 (Metasys); default: 3
H5-08 = 2, P1 (APOGEE FLN); default: 2
H5-08 = 3, BACnet; default: 3
H5-02
<1>
0
<1>
1
2
<1>
3
<1>
4
<1> Not available when H5-08 is set to 2 P1 (APOGEE FLN).
<2> Not available when H5-08 is set to 0 (MEMOBUS/Modbus) or 1 (Metasys N2).
n
H5-03: Communication Parity Selection
Sets the parity used for communications.
Note:
Cycle power for the setting to take effect.
No.
H5-03
Setting 0: No parity
Setting 1: Even parity
Setting 2: Odd parity
330
Name
Drive Slave Address
Name
Communication Speed Selection
Communication Speed
1200 bps
2400 bps
4800 bps
9600 bps
19200 bps
Name
Communication Parity Selection
Setting Range
0 to FFH
Setting Range
0 to 8
H5-02
<1>
5
<1>
6
<1>
7
<1> <2>
8
Setting Range
0 to 2
YASKAWA TOEP YAIZ1U 03B YASKAWA AC Drive – Z1000 User Manual
Default
1FH
Default
<1>
Communication Speed
38400 bps
57600 bps
76800 bps
115200 bps
Default
0