H2: Multi-Function Digital Outputs - YASKAWA Z1000U Series Programming Manual

Hvac matrix low harmonic drive for hvac applications
Hide thumbs Also See for Z1000U Series:
Table of Contents

Advertisement

Setting A9: PI2 Disable (N.C.)
Enables the secondary PI controller (when open, output behavior depends on the setting of S3-12).
Setting AA: PI2 Inverse Operation
Changes the sign of the secondary PI controller input (reverse acting PI control).
Setting AB: PI2 Integral Reset
Resets the secondary PI controller integral value.
Setting AC: PI2 Integral Hold
Locks the value of the secondary PI controller integral value.
Setting AD: Select PI2 Parameters
Uses the secondary PI controller Proportional and Integral adjustments (S3-06 and S3-07) instead of the primary PID controller
Proportional and Integral adjustments (b5-02 and b5-03). Only valid when S3-01 = 0 (secondary PI controller disabled).
Note:
This multi-function input has no effect on the secondary PI controller. It is only used for the primary PID controller (b5-oo).
Setting AE: BP Bypass Run
Commands a Run in Bypass mode via closing the BP Bypass Relay multi-function output.
Setting AF: Emergency Override Forward Run
Enables Emergency Override Forward Run.
Setting B0: Emergency Override Reverse Run
Enables Emergency Override Reverse Run.
Setting B1: Customer Safeties
The Customer Safeties multi-function input functionality is identical to Bypass Drive Enable (Setting 70: Drive Enable 2),
except for the following:
• When the input is open, the stopping method is forced to Coast to Stop
• If the input is open when the Run command is present, a "SAFE" alarm is displayed instead of the "dnE" alarm.
Setting B2: BAS Interlock
The BAS Interlock multi-function input is used in a damper interlock circuit to keep the drive from running until the damper
control relay is closed.
• When the input is open, the drive output is shut off (baseblocked).
• The drive will display an "inTLK" message if the input is open and a Run command is present. It will not display "dnE".
• The state of the BAS Interlock multi-function input has no effect on the Emergency Override multi-function inputs
(H1-oo = AF, B0). The Emergency Override command will be accepted if the BAS Interlock digital input is open or closed.
u

H2: Multi-Function Digital Outputs

n
H2-01 to H2-03: Terminal M1-M2, M3-M4, and MD-ME-MF Function Selection
The drive has three multi-function output terminals.
H2-02, and H2-03.
No.
H2-01
H2-02
H2-03
Terminal MD-ME-MF Function Selection (relay)
Setting
0
During Run
1
Zero Speed
2
Speed Agree 1
YASKAWA ELECTRIC SIEP C710636 10C Z1000U HVAC MATRIX Drive Programming Manual
Parameter Name
Terminal M1-M2 Function Selection (relay)
Terminal M3-M4 Function Selection (relay)
Table 1.32 Multi-Function Digital Output Terminal Settings
Function
Table 1.32
lists the functions available for theses terminals using H2-01,
Page
Setting
88
3
User-Set Speed Agree 1
88
4
Frequency Detection 1
89
5
Frequency Detection 2
1.7 H: Terminal Functions
Setting Range
0 to 1B6
0: During Run
0 to 1B6
1: Zero Speed
0 to 1B6
2: Speed Agree 1
Function
Default
1
Page
89
90
90
87