E2-01: Motor Rated Current
Provides motor control, protects the motor, and calculates torque limits. Set E2-01 to the full load amps (FLA) stamped on
the motor nameplate.
No.
E2-01
Note:
1. Display is in the following units: 5A0007 to 5A0017: 0.01 A units; 5A0022 to 5A0242: 0.1 A units.
2. An oPE02 error will occur if the motor rated current in E2-01 is set lower than the motor no-load current in E2-03. Set E2-03 correctly
to prevent this error.
n
E2-11: Motor Rated Power
Sets the motor rated power in kW. If Auto-Tuning completes successfully, the value entered to T1-02 will automatically be
saved to E2-11.
No.
E2-11
n
E5-02: Motor Rated Power
Sets the rated power of the motor. Determined by the value set to T2-04 during Stationary Auto-Tuning for PM motors.
No.
E5-02
n
E5-03: Motor Rated Current
Sets the motor rated current in amps. Automatically set when the value is entered to T2-06 during Auto-Tuning.
No.
E5-03
Note:
Display is in the following units: 5A0007 to 5A0017: 0.01 A units; 5A0022 to 5A0242: 0.1 A units.
n
E5-04: Number of Motor Poles
Sets the number of motor poles. Automatically set when the value is entered to T2-08 during Auto-Tuning.
No.
E5-04
n
E5-05: Motor Stator Resistance (r1)
Set the resistance for one motor phase. Do not enter the line-to-line resistance into E5-05 when measuring the resistance
manually.
No.
E5-05
n
E5-06: Motor d-Axis Inductance (Ld)
Sets the d-Axis inductance in 0.01 mH units.
No.
E5-06
YASKAWA TOEP YAIZ1U 03B YASKAWA AC Drive – Z1000 User Manual
Parameter Name
Motor Rated Current
Parameter Name
Motor Rated Power
Parameter Name
Motor Rated Power
Parameter Name
Motor Rated Current
Parameter Name
Number of Motor Poles
Parameter Name
Motor Stator Resistance
Parameter Name
Motor d-Axis Inductance
4.7 Basic Drive Setup Adjustments
Setting Range
10% to 200% of the drive
rated current
Setting Range
0.00 to 650.00 kW
Setting Range
0.10 to 370.00 kW
Setting Range
10 to 200% of drive rated
current
Setting Range
2 to 48
Setting Range
0.000 to 65.000 Ω
Setting Range
0.00 to 300.00 mH
Default
Determined by
o2-04
Default
Determined by
o2-04
Default
Determined by
o2-04
Default
Determined by
o2-04
Default
Determined by
o2-04
4
Default
Determined by
o2-04
Default
Determined by
o2-04
129