YASKAWA Z1000 User Manual page 353

Ac drive for hvac fan and pump
Hide thumbs Also See for Z1000:
Table of Contents

Advertisement

Drive Model
R/L1, S/L2, T/L3
U/T1, V/T2, W/T3
⊖, ⊕1, ⊕2
5A0009
B1, B2
R/L1, S/L2, T/L3
U/T1, V/T2, W/T3
⊖, ⊕1, ⊕2
5A0011
B1, B2
R/L1, S/L2, T/L3
U/T1, V/T2, W/T3
⊖, ⊕1, ⊕2
5A0017
B1, B2
R/L1, S/L2, T/L3
U/T1, V/T2, W/T3
⊖, ⊕1, ⊕2
5A0022
B1, B2
R/L1, S/L2, T/L3
U/T1, V/T2, W/T3
5A0027
⊖, ⊕1, ⊕2
5A0032
B1, B2
R/L1, S/L2, T/L3
U/T1, V/T2, W/T3
⊖, ⊕1
5A0041
B1, B2
YASKAWA TOEP YAIZ1U 03B YASKAWA AC Drive – Z1000 User Manual
Recomm. Gauge
Terminal
2
mm
(AWG, kcmil)
Wire Range
2
mm
(AWG, kcmil)
2.5
2.5 to 6.0
(14)
(14 to 10)
2.5
2.5 to 6.0
(14)
(14 to 10)
2.5 to 6.0
(14 to 10)
2.5 to 6.0
(14 to 10)
6.0
4.0 to 6.0
(10)
(12 to 10)
6.0
2.5 to 16
(10)
(14 to 6)
2.5
2.5 to 16
(14)
(14 to 6)
2.5 to 16
(14 to 6)
2.5 to 6.0
(14 to 10)
10
4.0 to 6.0
(8)
(12 to 8)
6.0
6.0 to 16
(10)
(10 to 6)
6.0
6.0 to 16
(10)
(10 to 6)
6.0 to 16
(10 to 6)
6.0 to 10
(10 to 8)
10
6.0 to 10
(8)
(12 to 8)
10
6.0 to 16
(8)
(10 to 6)
6.0
6.0 to 16
(10)
(10 to 6)
6.0 to 16
(10 to 6)
6.0 to 10
(10 to 8)
10
6.0 to 10
(8)
(10 to 6)
16
16 to 25
(6)
(6 to 4)
16
16 to 25
(6)
(6 to 4)
16 to 25
(6 to 4)
6.0 to 10
(10 to 8)
16
10 to 16
(6)
(10 to 6)
16
6.0 to 25
(6)
(10 to 3)
16
6.0 to 25
(6)
(10 to 3)
(6 to 1)
4.0 to 25
(12 to 3)
16
10 to 16
(6)
(6)
D.3 UL and CSA Standards
Screw
Tightening Torque
Size
N·m (lb.in.)
1.2 to 1.5
M4
(10.6 to 13.3)
2.1 to 2.3
M4
(18.6 to 20.4)
2.0 to 2.5
M5
(17.7 to 22.1)
3.6 to 4.0
(31.8 to 35.4)
M5
2.7 to 3.0
(23.9 to 26.6)
5.4 to 6.0
M6
(47.8 to 53.1)
3.6 to 4.0
(31.8 to 35.4)
M5
2.7 to 3.0
(23.9 to 26.6)
5.4 to 6.0
M6
(47.8 to 53.1)
5.4 to 6.0
M6
(47.8 to 53.1)
2.7 to 3.0
M5
(23.9 to 26.6)
5.4 to 6.0
M6
(47.8 to 53.1)
9.0 to 11
M8
(79.7 to 97.4)
D
353

Advertisement

Table of Contents
loading