A: Initialization Parameters; A1: Initialization - YASKAWA Z1000 User Manual

Ac drive for hvac fan and pump
Hide thumbs Also See for Z1000:
Table of Contents

Advertisement

B.1 A: Initialization Parameters
B.1 A: Initialization Parameters
Symbol
Parameter can be changed during run.
Parameter is ONLY available when operating the drive with Open Loop Vector for PM motors.
OLV/PM
OLV/PM
The A parameter group creates the operating environment for the drive. This includes the parameter Access Level, Motor
Control Method, Password, User Parameters and more.
u

A1: Initialization

No.
(Addr.
Name
Hex)
A1-00
(100)
Language Selection
<1>
A1-01
(101)
Access Level Selection
<2>
A1-02
Control Method
(102)
Selection
<1>
A1-03
Initialize Parameters
(103)
A1-04
Password
(104)
A1-05
Password Setting
(105)
A1-06
Application Preset
(127)
<1> Parameter setting value is not reset to the default value when the drive is initialized.
<2> Default setting value is dependent on the Application Preset selected with parameter A1-06.
270
Table B.1 Symbols and Icons Used in Parameter Descriptions
LCD Display
Select Language
0: English
0: English
1: Japanese
1:
(Japanese)
3: French
3: Français
5: Spanish
5: Español
6: Portuguese
6: Portuguêse
0: View and set A1-01 and A1-04.
Access Level
Uo-oo parameters can also be viewed.
0: Operation Only
1: User Parameters (access to a set of parameters selected by
1: User Parameters
the user, A2-01 to A2-32)
2: Advanced Level
2: Advanced Access (access to view and set all parameters)
0: V/f Control
Control Method
5: Open Loop Vector Control for PM
0: V/F Control
5: PM OpenLoop Vect
Init Parameters
0: No initialization
0: No Initialize
1110: User Initialize (parameter values must be stored using
1110: User Initialize
parameter o2-03)
2220: 2-Wire Initial
2220: 2-Wire Initialization
3330: 3-Wire Initial
3330: 3-Wire Initialization
3410: SELVAL
3410: HVAC Initialization
HVAC Initialize
3420: OEM Bypass Initialization
3420: SELVAL OEM
5550: oPE04 Fault Reset
Bypass Init
5550: Term Cntrl Int
When the value set into A1-04 does not match the value set
Enter Password
into A1-05, parameters A1-01 through A1-03, A1-06, and
A2-01 through A2-33 cannot be changed.
When the value set into A1-04 does not match the value set
Select Password
into A1-05, parameters A1-01 through A1-03, A1-06, and
A2-01 through A2-33 cannot be changed.
Application Sel
0: Standard
0: General
1: Fan
1: Fan General
2: Fan with PI Control
2: Fan PI
3: Return Fan with PI Control
3: Fan ReturnAir/PI
4: Cooling Tower Fan
4: Cooling Tower
5: Cooling Tower Fan with PI Control
5: CoolingTower/PI
6: Pump (Secondary)
6: Pump Secondary
7: Pump with PI Control
7: Pump PI
Description
Description
YASKAWA TOEP YAIZ1U 03B YASKAWA AC Drive – Z1000 User Manual
Values
Page
Default: 0
150
Range: 0 to 6
Default: 2
150
Range: 0 to 2
Default: 0
121
Range: 0, 5
Default: 0
Range: 0 to 3420,
151
5550
Default: 0000
Min.: 0000
Max.: 9999
Default: 0000
Min.: 0000
Max.: 9999
Default: 0
152
Range: 0 to 7

Advertisement

Table of Contents
loading

Table of Contents