H5-14, H5-15: BACnet Device Object Identifiers 0 and 1
These parameters set the Instance Identifier of the BACnet Device Object, where the H5-14 value is the least significant word
and the H5-15 value is the most significant word.
No.
H5-14
H5-15
Example 1: Set Device Object Instance Identifier of "1234"
1234 decimal is equal to 4D2H (hexadecimal)
Set H5-14 to 4D2H and set H5-15 to 0.
Example 2: Set Device Object Instance Identifier of "1234567"
12334567 decimal is equal to 12D687H
Set H5-14 to D687H and set H5-15 to 12H.
YASKAWA TOEP YAIZ1U 03B YASKAWA AC Drive – Z1000 User Manual
Name
BACnet Device Object Identifier 0
BACnet Device Object Identifier 1
C.4 BACnet Setup Parameters
Setting Range
0 to FFFFH
0 to 3FH
Default
1
0
C
333