YASKAWA Z1000 User Manual page 174

Ac drive for hvac fan and pump
Hide thumbs Also See for Z1000:
Table of Contents

Advertisement

4.13 Advanced Drive Setup Adjustments
n
H5-08: Communications Protocol Selection
Selects the communications protocol.
No.
H5-08
Setting 0: MEMOBUS/Modbus
Setting 1: N2 (Metasys)
Setting 2: P1 (APOGEE FLN)
Setting 3: BACnet
n
H5-09: Communications Fault Detection Time
Sets the time the communications must be lost before the drive triggers a CE fault.
No.
H5-09
n
H5-10: Unit Selection for MEMOBUS/Modbus Register 0025H
Sets the unit for the output voltage monitor value in MEMOBUS/Modbus register 0025H.
No.
H5-10
Unit Selection for MEMOBUS/Modbus Register 0025H
Setting 0: 0.1 V units
Setting 1: 1 V units
n
H5-11: Communications Enter Function Selection
Selects whether an Enter command is necessary to change parameter values via MEMOBUS/Modbus communications.
to Enter Command on page
No.
H5-11
Setting 0: Enter command necessary
Parameter changes become effective after an Enter command. An Enter command must only be sent after the last parameter
change, not for each single parameter.
Setting 1: Enter command not necessary
Parameter value changes become effective immediately without the need to send an Enter command.
n
H5-12: Run Command Method Selection
Selects the type of sequence used when the Run command source is set to MEMOBUS/Modbus communications
(b1-02, b1-16 = 2).
No.
H5-12
Setting 0: FWD/Stop, REV/Stop
Setting bit 0 of MEMOBUS/Modbus register 0001H will start and stop the drive in the forward direction. Setting bit 1 will
start and stop the drive in reverse.
Setting 1: Run/Stop, FWD/REV
Setting bit 0 of MEMOBUS/Modbus register 0001H will start and stop the drive. Setting bit 1 changes the direction.
n
L5-02: Auto Restart Fault Output Operation Selection
Determines if a fault output is triggered (H2-oo = E) when the drive attempts to restart.
No.
L5-02
174
Name
Communications Protocol Selection
Name
Communications Fault Detection Time
Name
341.
Name
Communications Enter Function Selection
Name
Run Command Method Selection
Name
Auto Restart Fault Output Operation Selection
Setting Range
0 to 3
Setting Range
0.0 to 10.0 s
Setting Range
0 or 1
Setting Range
0 or 1
Setting Range
0 or 1
Setting Range
0, 1
YASKAWA TOEP YAIZ1U 03B YASKAWA AC Drive – Z1000 User Manual
Default
0
Default
2.0 s
Default
0
Refer
Default
0
Default
0
Default
0

Advertisement

Table of Contents
loading

Table of Contents