L4: Speed Detection; L5: Fault Restart - YASKAWA Z1000 User Manual

Ac drive for hvac fan and pump
Hide thumbs Also See for Z1000:
Table of Contents

Advertisement

u

L4: Speed Detection

No.
(Addr.
Name
Hex)
L4-01
Speed Agreement
(499)
Detection Level
L4-02
Speed Agreement
(49A)
Detection Width
L4-03
Speed Agreement
(49B)
Detection Level (+/-)
Speed Agreement
L4-04
Detection Width
(49C)
(+/-)
Frequency Reference
L4-05
Loss Detection
(49D)
Selection
L4-06
Frequency Reference
(4C2)
at Reference Loss
L4-07
Speed Agreement
(470)
Detection Selection
u

L5: Fault Restart

No.
(Addr.
Name
Hex)
L5-01
Number of Auto Restart
(49E)
Attempts
Auto Restart Fault
L5-02
Output Operation
(49F)
Selection
L5-03
Time to Continue
(4A0)
Making Fault Restarts
L5-04
Fault Reset Interval
(46C)
Time
L5-05
Fault Reset Operation
(467)
Selection
YASKAWA TOEP YAIZ1U 03B YASKAWA AC Drive – Z1000 User Manual
LCD Display
L4-01 sets the frequency detection level for digital output
Spd Agree Level
functions H2-oo = 2, 3, 4, 5.
L4-02 sets the hysteresis or allowable margin for speed
Spd Agree Width
detection.
L4-03 sets the frequency detection level for digital output
Spd Agree Lvl+-
functions H2-oo = 13, 14, 15, 16.
L4-04 sets the hysteresis or allowable margin for speed
Spd Agree Wdth+-
detection.
Ref Loss Sel
0: Stop. Drive stops when the frequency reference is lost.
0: Stop
1: Run. Drive runs at a reduced speed when the frequency
1: Run@L4-06PrevRef
reference is lost.
Sets the percentage of the frequency reference that the drive
Fref at Floss
should run with when the frequency reference is lost.
Freq Detect Sel
0: No detection during baseblock.
0: No Detection @BB
1: Detection always enabled.
1: Always Detected
LCD Display
Sets the number of times the drive may attempt to restart after
Num of Restarts
the following faults occur: GF, LF, oC, ov, PF, oL1, oL2, oL3,
STo, Uv1.
Restart Sel
0: Fault output not active.
0: Flt Outp Disabld
1: Fault output active during restart attempt.
1: Flt Outp Enabled
Enabled only when L5-05 is set to 0. Causes a fault if a fault
Max Restart Time
restart cannot occur after the set time passes.
Sets the amount of time to wait between performing fault
Flt Reset Wait T
restarts.
0: Continuously attempt to restart while incrementing restart
Fault Reset Sel
counter only at a successful restart (same as F7 and G7).
0: Continuous
1: Attempt to restart with the interval time set in L5-04 and
1: Use L5-04 Time
increment the restart counter with each attempt (same as V7).
B.8 L: Protection Function
Description
Description
Values
Page
Default: 0.0 Hz
Min.: 0.0
Max.: 240.0
Default: 2.0 Hz
Min.: 0.0
Max.: 20.0
Default: 0.0 Hz
Min.: -240.0
Max.: 240.0
Default: 2.0 kHz
Min.: 0.0
Max.: 20.0
Default: 1
132
Range: 0, 1
Default: 80.0%
Min.: 0.0
132
Max.: 100.0
Default: 0
Range: 0, 1
Values
Page
Default: 0
Min.: 0
132
Max.: 10
Default: 0
174
Range: 0, 1
Default: 180.0 s
Min.: 0.0
132
Max.: 600.0
Default: 10.0 s
Min.: 0.5
175
Max.: 600.0
Default: 1
175
Range: 0, 1
B
301