YASKAWA Z1000 User Manual page 262

Ac drive for hvac fan and pump
Hide thumbs Also See for Z1000:
Table of Contents

Advertisement

A.2 Drive Specifications
Item
Motor Protection
Momentary Overcurrent
Protection
Overload Protection
Overvoltage Protection
Undervoltage Protection 600 V class: Stops when DC bus voltage falls below approx. 475 V
Protection
Functions
Momentary Power Loss
Ride-Thru
Heatsink Overheat
Protection
Stall Prevention
Ground Protection
DC Bus Charge LED
Area of Use
Ambient Temperature
Humidity
Storage Temperature
Environment
Altitude
Vibration/Shock
Standards
Protection Design
<1> The accuracy of these values depends on motor characteristics, ambient conditions, and drive settings. Specifications may vary with different motors
and with changing motor temperature. Contact Yaskawa for consultation.
<2> Overload protection may be triggered when operating with 150% of the rated output current if the output frequency is less than 6 Hz.
<3> May be shorter due to load conditions and motor speed.
<4> Ground protection cannot be provided when the impedance of the ground fault path is too low, or when the drive is powered up while a ground
fault is present at the output.
<5> Removing the top protective cover or bottom conduit bracket from an IP20/NEMA 1, UL Type 1 enclosure drive voids NEMA 1, UL Type 1
protection while maintaining IP20 conformity. This is applicable to models 5A0003 to 5A0242.
262
Electronic thermal overload relay
Drive stops when rated output current exceeds 175%
Drive stops after 60 s at 110% of rated output current
Drive stops after 0.5 s at 140% of rated output current
600 V class: Stops when DC bus voltage exceeds approx. 1040 V
Immediately stop after 15 ms or longer power loss
Continuous operation during power loss shorter than 2 s by speed search function
Thermistor
Stall Prevention is available during acceleration, deceleration, and during run.
<4>
Electronic circuit protection
Remains lit until DC bus voltage falls below 50 V
Indoors
-10 °C to +40 °C (14 to 104 °F) IP20/NEMA 1, UL Type 1 Enclosure
-10 °C to +50 °C (14 to 122 °F) IP00/Open Type Enclosure
95% RH or less (no condensation)
-20 °C to +70 °C (-4 to +158 °F) (short-term temperature during transportation)
Up to 1000 meters without derating, up to 3000 m with output current and voltage derating.
Altitude Derating on page 268
2
10 to 20 Hz: 9.8 m/s
2
20 to 55 Hz: 5.9 m/s
(5A0003 to 5A0099)
2
2.0 m/s
(5A0125 to 5A0242)
• UL508C
• IEC/EN 61800-5-1
• CSA
IP00/Open Type enclosure, IP20/NEMA 1, UL Type 1 enclosure
Specification
<2>
<2>
<3>
for details.