A.1 Power Ratings
A.1 Power Ratings
u

Three-Phase 600 V Class Drive Models 5A0003 to 5A0032

Item
Drive Models
Maximum Applicable Motor Capacity
<1>
(HP)
Input Current (A)
Rated Voltage
Rated Frequency
Allowable Voltage
Input
Fluctuation
Allowable Frequency
Fluctuation
Input Power (kVA)
Rated Output Capacity
<3> <4>
(kVA)
Rated Output Current
<4>
(A)
Overload Tolerance
Output
Carrier Frequency
Maximum Output
Voltage (V)
Maximum Output
Frequency (Hz)
<1> The motor capacity (HP) refers to a NEC rated 4-pole motor. The rated output current of the drive output amps should be equal to or greater than
the motor current. Select the appropriate capacity drive if operating the motor continuously above motor nameplate current.
<2> Assumes operation at the rated output current. Input current rating varies depending on the power supply transformer, input reactor, wiring
connections, and power supply impedance.
<3> Rated motor capacity is calculated with a rated output voltage of 575 V.
<4> Carrier frequency is set to 2 kHz. Current derating is required to raise the carrier frequency.
258
Table A.1 Power Ratings (Three-Phase 600 V Class)
5A0003
5A0004
2
3
<2>
3.6
5.1
4.1
5.8
2.7
3.9
2.7
3.9
Specification
5A0006
5A0009
5A0011
5
7.5
10
8.3
12
16
Three-phase 500 to 600 Vac 50/60 Hz
-10 (-15) to +10%
±5%
9.5
14
18
6.1
9
11
6.1
9
11
110% of rated output for 60 s
140% of rated output for 0.5 s
User adjustable between 1 and 12.5 kHz
Three-phase 500 to 600 Vac (proportional to input voltage)
240 Hz
YASKAWA TOEP YAIZ1U 03B YASKAWA AC Drive – Z1000 User Manual
5A0017
5A0022
5A0027
15
20
25
23
31
38
26
35
43
17
22
27
17
22
27
5A0032
30
45
51
32
32