E5ZE Temperature Controller Write Protocol
Write Alarm Temperature (Setting Unit 0.1) (Sequence No. 157
(Hex 009D))
Writes the alarm temperatures using a setting unit of 0.1 (5 digits)
Send Data Word Allocation (3rd Operand of PMCR(260))
First word of
send data
Receive Data Word Allocation (4th Operand of PMCR(260))
None.
530
+0
Number of send data words
+1
(Undefined)
+2
Alarm 1 set value (rightmost 4 digits)
Alarm 1 set value (leftmost 1 digit)
+3
+4
Alarm 2 set value (rightmost 4 digits)
+5
Alarm 2 set value (leftmost 1 digit)
~
+30
Alarm 1 set value (rightmost 4 digits)
+31
Alarm 1 set value (leftmost 1 digit)
+32
Alarm 2 set value (rightmost 4 digits)
+33
Alarm 2 set value (leftmost 1 digit)
Offset
Contents (data format)
+0
Number of send data words
(4 digits Hex)
+1
Unit No. (2 digits Hex)
+2
Channel 0
Alarm 1 set value (rightmost 4 digits)
(4 digits BCD)
+3
Channel 0
Alarm 1 set value (leftmost 1 digits)
(4 digits BCD)
+4
Channel 0
Alarm 2 set value (rightmost 4 digits)
(4 digits BCD)
+5
Channel 0
Alarm 2 set value (leftmost 1 digits)
(4 digits BCD)
+32
Channel 7
Alarm 2 set value (rightmost 4 digits)
(4 digits BCD)
+33
Channel 7
Alarm 2 set value (leftmost 1 digits)
(4 digits BCD)
Unit No.
Channel 0
~
Channel 7
0022 (0034 decimal) (fixed)
00 to 0F
0000 to 9999
0000 to 0009
0000 to 9999
0000 to 0009
0000 to 9999
0000 to 0009