Omron SYSMAC CS1W-SCB41-V1 Operation Manual page 359

Sysmac cs series; sysmac cj series. serial communications boards and serial communications units
Table of Contents

Advertisement

Troubleshooting
Error conditions
Serial communi-
Indicator
cations mode
display
The serial com-
---
munications
mode is set to no-
protocol mode.
330
Words allocated in CIO
Status and
other condi-
tions
---
The Reception Completed
Flag is OFF.
Board: Auxiliary Area bit
A35606/A35614 is OFF.
Unit: CIO Area word n+9/
n+19 bit 06 is OFF.
---
---
Cause
Area
Reception does
not complete due
to the following fac-
tors.
The start code/
end code setting
is incorrect.
No data has
been received.
The specified
number of data
bytes has not
been received.
Data of 260
bytes or more
was received in
the reception
buffer before the
RXD(235)/
RXDU(255)
instruction was
executed.
A hardware error
has occurred in the
reception circuit of
the Board/Unit.
Section 11-3
Remedy
---
Revise the set-
tings for the start
code/end code in
DM Area word
m+5/m+15.
Revise the speci-
fied number of
receive data bytes
in allocation DM
Area word m+5/
m+15.
Cycle the power or
restart the Board
and clear the
reception buffer.
Note: If an overrun
error occurs, the
Overrun Error Flag
can be turned OFF
by cycling the
power or restarting
the Unit/Board or
restarting the port.
Conduct a loop-
back test in serial
communications
mode to check the
transmission lines.
If an error occurs
during the test,
replace the Board
or Unit.