Setup Area Allocations - Omron SYSMAC CS1W-SCB41-V1 Operation Manual

Sysmac cs series; sysmac cj series. serial communications boards and serial communications units
Table of Contents

Advertisement

Setup Area Allocations

5-2-2
Setup Area Allocations
DM Area
Boards
(CS Series only)
(CS/CJ Series)
Port 1
Port 2
Port 1
D32000
D32010
m
D32001
D32011
m + 1
D32007
D32017
m + 7
D32008
D32018
m + 8
D32009
D32019
m + 9
Port Settings
154
Bit
Units
Port 2
m + 10
15
Port settings
0: Defaults, 1: User settings
12 to 14
Reserved
08 to 11
Serial communications mode
6: Protocol macro
05 to 07
Reserved
04
Start bits
(1 start bit is always used regardless of this setting)
03
Data length
02
Stop bits
01
Parity
00
Parity
m + 11
00 to 03
Baud rate (Unit: bps)
0: Default (9,600)
5: 4,800
(The following setting can be selected even if protocol macro is set
as the serial communications mode: Unit Ver. 1.2 or later only)
9: 57,600
m + 17
08 to 15
Serial Gateway response timeout monitoring time (Unit Ver. 1.2 or
later only)
0 hex: 5 s (default)
01 to FF hex (1 to 255 decimal): 0.1 to 25.5 s
Unit: 100 ms
00 to 07
Serial Gateway send start timeout monitoring time (Unit Ver. 1.2 or
later only)
0 hex: 5 s (default)
01 to FF hex (1 to 255 decimal): 0.1 to 25.5 s
Unit: 100 ms
m + 18
15
Transmission method
00 to 14
Reserved
03
Clearing/holding the contents of the reception buffer in full-duplex
mode (Unit Ver. 1.2 or later only)
0: Clear; 1: Hold
02
Link word specification data exchange timing (Unit Ver. 1.2 or later
only)
0: On-request I/O refreshing
1: Continuos I/O refreshing
00 to 01
Reserved
m + 19
00 to 15
Maximum number of bytes in send/receive data:
00C8 to 03E8 Hex
The setting for the port settings determines if the default settings or user set-
tings will be used for port 1 and port 2. Be sure to use the same settings as
the RS-232C port on the host computer connected via the Host Link System.
If the default port settings are specified, then the settings of bits 00 to 04 and
the baud rate in D32001 will be ignored.
The default settings used are as follows: Baud rate: 9,600 bps, start bits:
1 bit, data length: 7 bits, parity: even, and stop bits: 2 bits.
m = D30000 + 100 × unit number
Setting contents
0: 1 bit; 1: 1 bit
0: 7 bits; 1: 8 bits
0: 2 bits; 1: 1 bit
0: Yes; 1: No
0: Even; 1: Odd
3: 1,200
4: 2,400
6: 9,600
7: 19,200
8: 38,400
0: Half-duplex; 1: Full-duplex
Section 5-2